| Plan Review Notes For Permit 06091103 |
| Permit Number |
06091103 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-31 15:02:47 | ***DENIED*** | | | | | | 1) PLEASE INDICATE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING. | | | | | | 2) PLEASE SHOW TRAVEL DISTANCE DIMENSIONS ON LIFE | | | SAFETY PLANS. | | | | | | 3) ONLY (1) MEANS OF EGRESS IS ILLUSTRATED BUT (2) | | | EXITS ARE PROVIDED. | | | | | | 4) SEPARATE SHOP DRAWINGS ARE REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 5) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 6) FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL STATION | | | SERVICE. | | | | | | 7) CONSTRUCTION, ALTERATION AND DEMOLITION TO BE IN | | | COMPLIANCE WITH NFPA 241. | | | | | | 8) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE MOUNTED | | | NOT TO EXCEED 75' TRAVEL DISTANCE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 OR 804-4756 |
|