Plan Review Notes
Plan Review Notes For Permit 06091103
Permit Number 06091103
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-24 18:45:15****** UNSAT ***********
  
 ** PLEASE SEE PLANS ARE BEING SUBMITTED FOR 2ND FLR
 BUILD OUT.
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS BOUND
 TOGETHER INTO TWO COMPLETE SETS. PLEASE SEE SETS AS
 SUBMITTED ARE LOOSE AND FALLING APART INTO INDIVIDUAL
 SHEETS.
 FBC 106.1 ADMIN SECT.
  
 2) NOTE: PLEASE INDICATE THE FOLLOWING MINIMUM RELEVANT
 CODE FOR DESIGN AND COMPLIANCE.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2004 FBC.
  
 3) NOTE: PLEASE SEE MISSING INFORMATION FOR FBC CHAPTER
 13 FOR MIN CONTROLS OF LIGHTING FOR NEW SPACE/ BUILD
 OUT.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1.
 PLEASE INDICATE THE MAX TIMES OF ON THE TYPE OF DEVICES
 INSTALLED FOR OVER RIDES(4HRS MAX ON TIMER TYPE, 30MINS
 MAX ON OCCUPANT SENSOR TYPE).
 PLEASE INDICATE THE SCHEDULING IF USED ON A SYSTEM.
  
 4) NOTE: PLEASE INDICATE THE NEW OR EXISTING LIGHTING
 REQUIRED FOR EGRESS ON STAIRS. PLEASE SEE 7.8.1.3 AND
 7.9.2.2 FOR NORMAL AND EMERGENCY.
  
 5) NOTE: PLEASE SEE SOME SYMBOLS SHOWN ON PLANS WHICH
 ARE NOT SHOWN ON LEGEND?
  
 6) NOTE: PLEASE SEE RISER AND PANELS ARE MIS-LABLED.
 LA/LB, "A" AND "B".
 106.1.2 FBC ADMIN SECT
  
 7) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM /
 EXT LTS WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
  
 8) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS
 WERE DERIVED.
 220.3,220.10,220.11,220.13,
  
 9) NOTE: PLEASE SEE ROOF TOP GFI RECEPT IS BEING SHOWN
 CIRCUITEDTO THE CU, WHICH IS NOT PERMITTED.
 THIS IS REQUIRED TO CONTAIN A NEUTRAL ETC.
 2002 NEC.(TOO MANY SECTIONS TO LIST)
  
 10) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. ROOM USAGES FOR LOCATION OF THE ELECTRICAL
 PANELS NEEDS TO BE DECLARED.
 110.26, 240.24, 408.7 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-10-23 20:21:35IN ELEC FOR REVIEW.