| 2006-10-25 16:54:57 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB |
| | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE |
| | NOT AUTOMATIC OR POWER ASSISTED SHALL BE AS SHOWN IN |
| | FIGURE 11-25, FBC11-4.13.6.SHOW MANEUVERING |
| | CLEARANCE, PULL SIDE, DOORS 103 AND 107. |
| | |
| | 2.) FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| | FS553.79 (2), ATTACHED LETTER FROM DCA. |
| | |
| | 3.)IT APPEARS THAT WINDOWS 121 AND 118 ARE BEING |
| | REPLACED.DECLARE WIND DESIGN CRITERIA FBC1603.1.4, |
| | PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD |
| | FBC*106.3.3. |
| | |
| | 4.)DECLARE INTERIOR FINISH CLASSIFICATION, FBC TABLE |
| | 803.5. |
| | |
| | 5.)THE LIFE SAFETY PLAN DOESN'T HAVE ANY DIMENSIONS |
| | ON IT, PLEASE PROVIDE. |
| | |
| | 6.)PROVIDE DESIGN LOAD INFORMATION FOR THE MECHANICAL |
| | EQUIPMENT ON THE ROOF. |
| | |
| | 7.)FBC TABLE 601, TYPE IIIA REQUIRES 1 HOUR ON THE |
| | ROOF AND THE FLOORS.MECHANICAL AND PLUMBING SHEETS |
| | SHOW PENETRATIONS.PENETRATIONS ARE TO COMPLY WITH |
| | SECTION 712. |
| | |
| | 8.)THE SCHEDULE ON M-2.01 IS NOT CONSISTENT WITH FBC |
| | TABLE 1509.7.IT IS NOT CLEAR AS TO DISTANCE |
| | REQUIREMENTS FOR DIMENSIONS BETWEEN THE CATEGORIES. |
| | |
| | 9.)THE SQUARE FOOT AREA ON THE ENERGY CALCS DO NOT |
| | MATCH THE ARCHITECTURALS.THEY SHOULD BE THE SAME. |
| | |
| | 10.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALCS, |
| | FBC13-103.1. |