2006-10-25 16:54:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER ASSISTED SHALL BE AS SHOWN IN
 FIGURE 11-25, FBC11-4.13.6.SHOW MANEUVERING
 CLEARANCE, PULL SIDE, DOORS 103 AND 107.
  
 2.) FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2), ATTACHED LETTER FROM DCA.
  
 3.)IT APPEARS THAT WINDOWS 121 AND 118 ARE BEING
 REPLACED.DECLARE WIND DESIGN CRITERIA FBC1603.1.4,
 PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD
 FBC*106.3.3.
  
 4.)DECLARE INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 5.)THE LIFE SAFETY PLAN DOESN'T HAVE ANY DIMENSIONS
 ON IT, PLEASE PROVIDE.
  
 6.)PROVIDE DESIGN LOAD INFORMATION FOR THE MECHANICAL
 EQUIPMENT ON THE ROOF.
  
 7.)FBC TABLE 601, TYPE IIIA REQUIRES 1 HOUR ON THE
 ROOF AND THE FLOORS.MECHANICAL AND PLUMBING SHEETS
 SHOW PENETRATIONS.PENETRATIONS ARE TO COMPLY WITH
 SECTION 712.
  
 8.)THE SCHEDULE ON M-2.01 IS NOT CONSISTENT WITH FBC
 TABLE 1509.7.IT IS NOT CLEAR AS TO DISTANCE
 REQUIREMENTS FOR DIMENSIONS BETWEEN THE CATEGORIES.
  
 9.)THE SQUARE FOOT AREA ON THE ENERGY CALCS DO NOT
 MATCH THE ARCHITECTURALS.THEY SHOULD BE THE SAME.
  
 10.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALCS,
 FBC13-103.1.