| Plan Review Notes For Permit 06091088 |
| Permit Number |
06091088 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-13 14:29:54 | BUILDING REVIEW SECOND CHECKLIST: | | | 1- COMPLETE RAS 117 CALCULATIONS WERE REQUESTED ON | | | PREVIOUS CHECKLIST TO SHOW FASTENER SPACING THAT MEETS | | | THE CALCULATED DESIGN PRESSURES. CALCULATIONS WERE NOT | | | SUBMITTED. INSTEAD AN ENGINEER'SRECOMMENDED FASTENER | | | SPACING WAS PROVIDED. | | | | | | 2- FASTENER SPACING FROM FEDERAL ENGINEERING & TESTING | | | DOESN'T WORK TO MEET THE CALCULATED DESIGN PRESSURES. | | | ENGINEER TO PROVIDE COMPLETE RAS 117 CALCULATIONS TO | | | SHOW HOW THE RECOMMENDED FASTENING PATTERN MEETS THE | | | CALCULATED DESIGN PRESSURES. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 3- FEDERAL ENGINEERING & TESTING ENGINEERINGNEEDS TO | | | PROVIDE THE FIRM'S CERTIFICATE OF AUTHORIZATION NUMBER | | | AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE SEC. | | | 61G15-23.002. SEE ATTACHED COPY. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|