| Plan Review Notes For Permit 06091088 |
| Permit Number |
06091088 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-02 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- NOTICE OF COMMENCEMENT IS INCOMPLETE. | | | THERE IS NOT INFORMATION GIVEN FOR | | | CONTRACTOR. COMPLETE ALL INFORMATION AND | | | RE-RECORD NOTICE OF COMMENCEMENT. | | | | | | 2- BASE SHEET FASTENER SPACING PROVIDED | | | FOR WOOD DECK DOESN'T WORK. PROVIDE | | | COMPLETE RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 TO | | | SHOW FASTENER SPACING THAT MEETS THE | | | CALCULATED DESIGN PRESSURES. | | | | | | ***NOTES: | | | A) TAKE INTO CONSIDERATION THAT THE | | | MIN. FASTENER SEPARATION SHALL NOT BE | | | LESS THAN 4" O.C.. SEE SECTION 8.1 FROM | | | RAS 117 STANDARD. | | | B) THERE IS NOT NEED TO USE RAS 120 | | | STANDARD TO GET THE ROOF DESIGN | | | PRESSURES. TABLE 1609.6B FROM 2004 | | | FLORIDA BUILDING CODE CAN BE USED ALSO. | | | THE CITY OF WPB IS LOCATED IN BUILDING | | | EXPOSURE B WITH 140MPH WIND LOAD. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|