2007-06-19 11:29:19*** PROVISO/REVISION NEEDED ***
  
 1) NOTE: PLEASE SUBMIT LOAD CALCULATIONS CODE COMPLIANT
 TO 220.31B UNDER THE 2002 NEC>
 PLEASE SEE THE TOTAL LOAD SHOWN ON PANEL B IS
 SUBSTANTIALLY HIGHER THAN THAT OF THE LOAD SHOWN ON THE
 LOAD CALCULATIONS.
 PLEASE ALSO SEE THE LOAD SHOWN ON PANEL SCHEDULE FOR
 AHU AND HEAT DOES NOT CORRELATE WITH THE LOAD
 CALCULATIONS.
  
 ** PLEASE REVISE AND SUBMIT THIS REVISION ALONG WITH
 ANY OTHER REVISIONS BEFORE ANY ROUGH ELECTRICAL
 INSPECTION.
 PLEASE KNOW IF PLANS ARE NOT REVISED BY ROUGH, THE
 PERMIT FOR BUILDING WILL BE PLACED INTO A HOLD STATUS
 UNTIL COMMENTS ARE ADDRESSED. THIS CORRECTED REVISION
 MAY BE SUBMITTED AS SOON AS POSSIBLE ONCE PERMIT IS
 ISSUED.
  