| 2007-06-19 11:29:19 | *** PROVISO/REVISION NEEDED *** | | | | | | 1) NOTE: PLEASE SUBMIT LOAD CALCULATIONS CODE COMPLIANT | | | TO 220.31B UNDER THE 2002 NEC> | | | PLEASE SEE THE TOTAL LOAD SHOWN ON PANEL B IS | | | SUBSTANTIALLY HIGHER THAN THAT OF THE LOAD SHOWN ON THE | | | LOAD CALCULATIONS. | | | PLEASE ALSO SEE THE LOAD SHOWN ON PANEL SCHEDULE FOR | | | AHU AND HEAT DOES NOT CORRELATE WITH THE LOAD | | | CALCULATIONS. | | | | | | ** PLEASE REVISE AND SUBMIT THIS REVISION ALONG WITH | | | ANY OTHER REVISIONS BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION. | | | PLEASE KNOW IF PLANS ARE NOT REVISED BY ROUGH, THE | | | PERMIT FOR BUILDING WILL BE PLACED INTO A HOLD STATUS | | | UNTIL COMMENTS ARE ADDRESSED. THIS CORRECTED REVISION | | | MAY BE SUBMITTED AS SOON AS POSSIBLE ONCE PERMIT IS | | | ISSUED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH. | | | 561-805-6717 | | | [email protected] |
|