Plan Review Notes
Plan Review Notes For Permit 06091073
Permit Number 06091073
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-24 17:40:14*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE COMMENTS FROM THE PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON THE REVISED RISER AND REVISED PANEL
 SCHEDULE(S) SUBMITTED.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: NO, SEE COMMENT BELOW.
  
 ** PREVIOUS REVIEW NOTE #4**
 PLEASE SEE POSSIBLE MISSING GFI FOR KITCHEN COUNTER
 SPACE. 210.52C1,210.8A6.
  
 5) NOTE:NO, PLEASE STILL SEE MISSING RECEPTACLE IN
 KITCHEN FOR 2FT OR MORE OF WALL SPACE.
  
 ** PREVIOUS REVIEW NOTE #5 **
 PLEASE SEE SOME MISSING RECEPTS PER 210.52 AS THESE
 ROOMS WHERE ELECTRICAL IS TAKING PLACE APPEAR TO BE
 REWIRED?
 PLEASE KNOW, DUE TO THE ALTERATION IN DWELLING, PLEASE
 INDICATE EXISTING RECEPTS (E) .
 FBC 106.1.2 ADMIN SECT.
  
 6) NOTE: NO, PLEASE SEE THREE SETS OF PLANS ARE BEING
 SUBMITTED. PLEASE SEE ALL THREE ARE NEW AND ARE SIGNED,
 DATED AND SEALED BY THE ARCHITECT; HOWEVER THE THIRD
 SET OF PLANS ARE NOT SIGNED, DATED OR SEALED BY THE
 ENGINEER. PLEASE KNOW THAT ONLY TOW SETS ARE REQUIRED,
 HOWEVER IF THREE SETS ARE BEING SUBMITTED FOR REVIEW
 AND FOR STAMPING THEN ALL THREE SETS ARE REQUIRED TO BE
 SIGNED , DATED AND SEALED. FS 471.025, FAC
 61G15-23.002.
  
 ** PREVIOUS REVIEW NOTE #6**
 PLEASE SEETHERE ARE A COUPLE OF SEALS FROM ENGINEER
 WHICH ARE NOT CLEAR AND VISIBLE WITH ALL INFORMATION ON
 SAID SEAL.
 FS 471.025
  
 7) NOTE: OK.
  
 8) NOTE:NO, PLEASE SEE NEW RISER NOTES FOR REVISED
 RISER SUBMITTED. PLEASE SEE AS SHOWN, THIS SERVICE IS
 BEING DONE A 250 AMP SERVICE. PLEASE SEE 310.15B6 FOR
 MINIMUM SIZES FOR THE SEC?S.
 ** PLEASE CALL TO GO OVER THIS COMMENT.
  
 ** PREVIOUS REVIEW NOTE #8**
 PLEASE SEE SERVICE ENTRANCE CONDUCTORS SHALL BE SIZED
 PER 310.15B6 AT A MINIMUM. SERVICE SHOWN IS 250A'S.
 240.4
  
 9) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE #9**
 PLEASE ADJUST METER CAN SIZE FOR SERVICE (300A MIN).
 110.3, 90.7, 240.4
  
 10) NOTE: NO, SAME NOTE DEPENDING ON THE OUTCOME OF THE
 SERVICE BEING PROVIDED. AS SHOWN THE GEC IS TOO SMALL.
  
 ** PREVIOUS PLEASE SEE 250.66 AS THE MIN SIZE OF THE
 GROUNDING ELECTRODE CONDUCTOR SHALL BE #2 BASED ON THE
 NEW SEC'S WHICH WILL BE REQUIRED FOR THE SERVICE SIZE
 AS SHOWN.
  
 11) NOTE: NO, PLEASE SEE THERE ARE SOME CIRCUITS NOW
 BEING SHOWN FOR THE EXISTING PANEL WHICH SEEM TO BE
 DEDICATED/MOTOR/APPLIANCE CIRCUITS; HOWEVER IT IS
 UNCLEAR WHERE THESE ARE FIGURED INTO THE MAIN LOAD
 CALCULATIONS.
  
  
 ** PREVIOUS REVIEW NOTE #11**
 PLEASE PROVIDE PANEL SCHEDULE AND LOAD INFORMATION FOR
 EXISTING PANEL"A". SEEMS TO BE ONLY A 5A DIFFERENCE
 IN LOAD.
 240.4, 220.31B
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE:NO, PLEASE SEE THIS ELECTRIC WATER HEATER IS
 STILL SHOWN IN THE CLOSET.
  
 ** PREVIOUS REVIEW NOTE #14**
 PLEASE SEE 422.17, AS THE ELEC HWH SEEMS TO BE SHOWN IN
 THE CLOTHES CLOSET. PLEASE PROVIDE MIN SEPARATION
 REQUIRED OR RELOCATE.
  
 15) NOTE: OK.
  
 *** NEW NOTES ***
  
  
 16) NOTE: PLEASE CORRELATE RISER DIAGRAM AND PANELS.
 PLEASE SEE THE RISER SHOWS A 100A MBC PANEL, PANEL
 SHOWS A 100A PANEL WITH A 150A MCB AND SHOWS A 60AMP
 MAIN BREAKER BEING BACK-FED.????
 PLEASE SEE OF THIS 60A BREAKER IS NOT THE SERVICE
 ENTRANCE RATED MAIN, PLEASE SUBMIT DETAILS IF INDEED
 THIS IS THE CASE.
 17) NOTE: PLEASE CORRELATE FEEDERS /SERVICE ENTRANCE
 CONDUCTORS TO THIS EXISTING PANEL AND NEW PANEL. PLEASE
 SEE PANEL SCHEDULE INDICATES THESE AS FEEDERS, WHEN
 THEY ARE SERVICE ENTRANCE CONDUCTORS. PLEASE ALSO SEE
 THE CONDUCTORS ON RISER DO NOT CORRELATE WITH THAT OF
 THE PANEL SCHEDULE WHICH SHOWS A DIFFERENT CONDUCTOR
 SIZE.
  
 18) NOTE: PLEASE SEE RISER IS SHOWING *EQUIPMENT
 GROUNDING CONDUCTORS* FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED. PLEASE SEE 250.6,
 AND 250.24B. PLEASE SEE THIS IS PARALLELING THE
 NEUTRAL.
  
 19) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY BEING GIVEN AS A NOTICE AT
 THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  