| Plan Review Notes For Permit 06091073 |
| Permit Number |
06091073 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-17 09:09:22 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY | | | OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2 . | | | | | | 2) MANUAL J CALCULATIONS ARE CALLING FOR 22,281 | | | SENSIBLE BTU'S, AND THE MECH. PLANS ARE CALLING FOR | | | 48,900 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL FOR 20% | | | MORE THAN THE MANUAL J CAL'S, PER 2004 FBC | | | 13-607.1.ABC.1.1, PLEASE CORRECT. | | | | | | 3) THE MECH. PLANS ARE CALLING FOR A 6 KW HEATER, AND | | | THE ELECT. PLANS ARE CALLING FOR A 10 KW HEATER, THE | | | TWO MUST COINCIDE, PLEASE CORRECT. | | | | | | 4) SEE PAGE M-3 CONDENSER UNIT DETAIL, A METAL BAND MAY | | | NOT GO OVER THE CONDENSER UNIT, PLEASE CORRECT. | | | | | | 5) SEE PAGE M-1 FIRST FLOOR MASTER SUITE, 20X20 RAG | | | DUCT IS NOT SIZED, PLEASE CORRECT. NOTE IF THE AHU | | | CLOSET IS AN OPEN RETURN WITH A LOUVERED DOOR THAN THE | | | RETURN AIR DUCT WOULD NOT BE NEEDED . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|