2006-10-17 09:09:22*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2 .
  
 2) MANUAL J CALCULATIONS ARE CALLING FOR 22,281
 SENSIBLE BTU'S, AND THE MECH. PLANS ARE CALLING FOR
 48,900 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL FOR 20%
 MORE THAN THE MANUAL J CAL'S, PER 2004 FBC
 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 3) THE MECH. PLANS ARE CALLING FOR A 6 KW HEATER, AND
 THE ELECT. PLANS ARE CALLING FOR A 10 KW HEATER, THE
 TWO MUST COINCIDE, PLEASE CORRECT.
  
 4) SEE PAGE M-3 CONDENSER UNIT DETAIL, A METAL BAND MAY
 NOT GO OVER THE CONDENSER UNIT, PLEASE CORRECT.
  
 5) SEE PAGE M-1 FIRST FLOOR MASTER SUITE, 20X20 RAG
 DUCT IS NOT SIZED, PLEASE CORRECT. NOTE IF THE AHU
 CLOSET IS AN OPEN RETURN WITH A LOUVERED DOOR THAN THE
 RETURN AIR DUCT WOULD NOT BE NEEDED .
  