| 2006-10-16 19:47:56 | ********* UNSAT *********** |
| | |
| | 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON |
| | THE PLANS. 2002 NFPA-70 (NEC) , 2002 NFPA-72. FA CODE. |
| | |
| | 2) NOTE: PLEASE VERIFY THE SMOKE DEVICES BEING |
| | INSTALLED AS SHOWN. PLEASE SEE NFPA-72 ABOVE |
| | DEFINITIONS FOR SD (SMOKE DETECTORS) AND SA'S (SMOKE |
| | ALARMS). PLEASE ADJUST NOTE ON PLANS AND SYMBOLS. IT |
| | SEEM THESE MAY INDEED BE SA'S. |
| | |
| | 3) NOTE: PLEASE CLARIFY REQUIREMENTS FOR 210.70 LS 101 |
| | 7.8 AS SOME AREAS/ ROOMS SEEM TO SHOW A FAN ONLY BEING |
| | INSTALLED FOR EGRESS LTS WHERE SOME SORT OF FIXTURE IS |
| | REQUIRED. PLEASE KNOW, EITHER FAN AND AND LT KIT WILL |
| | BE REQUIRED OR 1/2 SW RECEPT ETC OR ONLY LT. |
| | |
| | 4) NOTE; PLEASE SEE POSSSIBLE MISSING GFI FOR KITCHEN |
| | COUNTER SPACE. 210.52C1, 210.8A6. |
| | |
| | 5) NOTE: PLEASE SEE SOME MISSING RECEPTS PER 210.52 AS |
| | THESE ROOMS WHERE ELECTRICAL IS TAKING PLACE APPEAR TO |
| | BE REWIRED.? |
| | PLEASE KNOW , DUE TO THE ALTERATION IN DWELLING, PLEASE |
| | INDICATE EXISTING RECEPTS (E) . |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 6) NOTE: PLEASE SEETHERE ARE A COUPLE OF SEALS FROM |
| | ENGINEER WHICH ARE NOT CLEAR AND VISABLE WITH ALL |
| | INFORMATION ON SAID SEAL. |
| | FS 471.025 |
| | |
| | 7) NOTE: PLEASE VERIFY THE KW RATING FOR AHU, AS THE |
| | LOAD CALCULATIONS SHOW 10KW, YET PANEL SCHEDULE AND OCP |
| | DO NOT CORRELATE. |
| | PLEASE SEE 424.3B , 240.4, 310.16 FOR ANY ADJUSTMENTS. |
| | PLEASE SEE MECH PLANS AS THESE ALSO ONLY SHOW 6KW? FOR |
| | THIS SIZE HOUSE? |
| | |
| | 8) NOTE: PLEASE SEE SERVICE ENTRANCE CONDUCTORS SHALL |
| | BE SIZED PER 310.15B6 AT A MINIMUM. SERVICE SHOWN IS |
| | 250A'S. |
| | 240.4 |
| | |
| | 9) NOTE: PLEASE ADJUST METER CAN SIZE FOR SERVICE (300A |
| | MIN). |
| | 110.3, 90.7, 240.4 |
| | |
| | 10) NOTE: PLEASE SEE 250.66 AS THE MIN SIZE OF THE |
| | GROUNDING ELECTRODE CONDUCTOR SHALL BE #2 BASED ON THE |
| | NEW SEC'S WHICH WILL BE REQUIRED FOR THE SERVICE SIZE |
| | AS SHOWN. |
| | |
| | 11) NOTE: PLEASE PROVIDE PANEL SCHEDULE AND LOAD |
| | INFORMATION FOR EXISTING PANEL"A". SEEMS TO BE ONLY A |
| | 5A DIFFERENCE IN LOAD. |
| | 240.4, 220.31B |
| | |
| | 12) NOTE: PLEASE SEE THAT THE NEW FOOTER STEEL WILL BE |
| | REQUIRED TO BE PART OF THE NEW GROUNDING ELECTRODE |
| | SYSTEM. 250.50, PLEASE SHOW. |
| | |
| | 13) NOTE: PLEASE SEE MISSING SA'S LEADING TO FLOOR |
| | ABOVE IN THE IMMEDIATE VICINITY OF THE STAIRS AND AT |
| | THE 2ND FLR LEVEL AS REQUIRED PER NFPA-72 11.5.1.1, |
| | 11.8.3, 2004 FBC R313 |
| | |
| | 14) NOTE: PLEASE SEE 422.17, AS THE ELEC HWH SEEMS TO |
| | BE SHOWN IN THE CLOTHES CLOSET. PLEASE PROVIDE MIN |
| | SEPARATION REQUIRED OR RELOCATE. |
| | |
| | 15) NOTE: PLEASE PROVIDE THE PANEL SCHEDULE WITH |
| | SPECIFIC AREAS AND ROOMS IN WHICH CIRCUITS FEED."IE": |
| | MASTER BEDRM LTS, MASTER BDRM RECEPTS, LIVING RM LTS, |
| | DINING RM RECEPTS.ETC. |
| | 408.4, 310.16. |
| | IT IS KNOW TO THIS OFFICE THAT CIRCUITING WILL MOST |
| | LIKELY BE REVISED AND CHANGED DURING CONSTRUCTION, |
| | HOWEVER THIS IS REQUIRED AT THIS TIME AND CANE REVISE |
| | PANEL SCHEDULE AT A LATE DATE. |
| | |
| | ** PLEASE SEE ONE SET OF THE ELECTRICAL PLANS SUBMITTED |
| | ARE REDLINED AT MANY AREAS AS NOTED ABOVE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |