Plan Review Notes
Plan Review Notes For Permit 06091073
Permit Number 06091073
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-16 19:47:56********* UNSAT ***********
  
 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON
 THE PLANS. 2002 NFPA-70 (NEC) , 2002 NFPA-72. FA CODE.
  
 2) NOTE: PLEASE VERIFY THE SMOKE DEVICES BEING
 INSTALLED AS SHOWN. PLEASE SEE NFPA-72 ABOVE
 DEFINITIONS FOR SD (SMOKE DETECTORS) AND SA'S (SMOKE
 ALARMS). PLEASE ADJUST NOTE ON PLANS AND SYMBOLS. IT
 SEEM THESE MAY INDEED BE SA'S.
  
 3) NOTE: PLEASE CLARIFY REQUIREMENTS FOR 210.70 LS 101
 7.8 AS SOME AREAS/ ROOMS SEEM TO SHOW A FAN ONLY BEING
 INSTALLED FOR EGRESS LTS WHERE SOME SORT OF FIXTURE IS
 REQUIRED. PLEASE KNOW, EITHER FAN AND AND LT KIT WILL
 BE REQUIRED OR 1/2 SW RECEPT ETC OR ONLY LT.
  
 4) NOTE; PLEASE SEE POSSSIBLE MISSING GFI FOR KITCHEN
 COUNTER SPACE. 210.52C1, 210.8A6.
  
 5) NOTE: PLEASE SEE SOME MISSING RECEPTS PER 210.52 AS
 THESE ROOMS WHERE ELECTRICAL IS TAKING PLACE APPEAR TO
 BE REWIRED.?
 PLEASE KNOW , DUE TO THE ALTERATION IN DWELLING, PLEASE
 INDICATE EXISTING RECEPTS (E) .
 FBC 106.1.2 ADMIN SECT.
  
 6) NOTE: PLEASE SEETHERE ARE A COUPLE OF SEALS FROM
 ENGINEER WHICH ARE NOT CLEAR AND VISABLE WITH ALL
 INFORMATION ON SAID SEAL.
 FS 471.025
  
 7) NOTE: PLEASE VERIFY THE KW RATING FOR AHU, AS THE
 LOAD CALCULATIONS SHOW 10KW, YET PANEL SCHEDULE AND OCP
 DO NOT CORRELATE.
 PLEASE SEE 424.3B , 240.4, 310.16 FOR ANY ADJUSTMENTS.
 PLEASE SEE MECH PLANS AS THESE ALSO ONLY SHOW 6KW? FOR
 THIS SIZE HOUSE?
  
 8) NOTE: PLEASE SEE SERVICE ENTRANCE CONDUCTORS SHALL
 BE SIZED PER 310.15B6 AT A MINIMUM. SERVICE SHOWN IS
 250A'S.
 240.4
  
 9) NOTE: PLEASE ADJUST METER CAN SIZE FOR SERVICE (300A
 MIN).
 110.3, 90.7, 240.4
  
 10) NOTE: PLEASE SEE 250.66 AS THE MIN SIZE OF THE
 GROUNDING ELECTRODE CONDUCTOR SHALL BE #2 BASED ON THE
 NEW SEC'S WHICH WILL BE REQUIRED FOR THE SERVICE SIZE
 AS SHOWN.
  
 11) NOTE: PLEASE PROVIDE PANEL SCHEDULE AND LOAD
 INFORMATION FOR EXISTING PANEL"A". SEEMS TO BE ONLY A
 5A DIFFERENCE IN LOAD.
 240.4, 220.31B
  
 12) NOTE: PLEASE SEE THAT THE NEW FOOTER STEEL WILL BE
 REQUIRED TO BE PART OF THE NEW GROUNDING ELECTRODE
 SYSTEM. 250.50, PLEASE SHOW.
  
 13) NOTE: PLEASE SEE MISSING SA'S LEADING TO FLOOR
 ABOVE IN THE IMMEDIATE VICINITY OF THE STAIRS AND AT
 THE 2ND FLR LEVEL AS REQUIRED PER NFPA-72 11.5.1.1,
 11.8.3, 2004 FBC R313
  
 14) NOTE: PLEASE SEE 422.17, AS THE ELEC HWH SEEMS TO
 BE SHOWN IN THE CLOTHES CLOSET. PLEASE PROVIDE MIN
 SEPARATION REQUIRED OR RELOCATE.
  
 15) NOTE: PLEASE PROVIDE THE PANEL SCHEDULE WITH
 SPECIFIC AREAS AND ROOMS IN WHICH CIRCUITS FEED."IE":
 MASTER BEDRM LTS, MASTER BDRM RECEPTS, LIVING RM LTS,
 DINING RM RECEPTS.ETC.
 408.4, 310.16.
 IT IS KNOW TO THIS OFFICE THAT CIRCUITING WILL MOST
 LIKELY BE REVISED AND CHANGED DURING CONSTRUCTION,
 HOWEVER THIS IS REQUIRED AT THIS TIME AND CANE REVISE
 PANEL SCHEDULE AT A LATE DATE.
  
 ** PLEASE SEE ONE SET OF THE ELECTRICAL PLANS SUBMITTED
 ARE REDLINED AT MANY AREAS AS NOTED ABOVE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717