| 2008-03-07 12:26:09 | ** DENIED REVIEWFOR REVISION ** |
| | |
| | ** PLEASE SEE SEVERAL ITEMS FROM ORIGINAL *PROVISO* |
| | GIVEN ON 5/8/07 HAVE NOT BEEN ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL AS |
| | PART OF THE GROUNDING ELECTRODE SYSTEM. |
| | 250.50 |
| | |
| | 2) NOTE: PLEASE SEE MISSING REFLECTED CODES TO BE |
| | STATED ON PLANS. |
| | 2005 NFPA-70 |
| | 2004 FBC W/2006 REVISIONS |
| | 2002 NFPA-72 |
| | |
| | 3) NOTE: PLEASE SEE THE CIRCUITING FOR DINING ROOM |
| | RECEPTACLES ARE STILL SHOWING #14 AWG AND 15AMP |
| | BREAKERS WHEN THE CODE SPECIFICALLY REQUIRE THE MINIMUM |
| | OF 20AMP AND #12 AWG. |
| | THIS WAS REDLINED ON PREVIOUS PLANS ISSUED FOR PERMIT |
| | AND STILL HAS NOT BEEN CHANGED. |
| | |
| | 4) NOTE: PLEASE SEE THE LOADS WHICH ARE REQUIRED TO BE |
| | FIGURED INTO LOAD CALCULATIONS FOR DINING ROOM CIRCUITS |
| | SHALL BE PER 220.52, 210.11C1 AND 210.52B1 |
| | ** MINIMUM 1500VA FOR EACH AND THIS LOAD SHALL BE IN |
| | ADDITION TO ANY OTHER SMALL APPLIANCE CIRCUITS. |
| | ON PREVIOUS REVIEW AND REDLINED ON PLANS WITH |
| | PROVISO*. |
| | |
| | 5) NOTE: PLEASE SEE THE REFRIGERATOR CIRCUIT WHICH |
| | STILL SHOWS #14 AWG WITH 20AMP BREAKER WHICH IS NOT |
| | PERMITTED. |
| | 240.4, 310.16 ETC |
| | ** NOTED ON PREVIOUS REVIEW AND REDLINED ON PLANS ALONG |
| | WITH PROVISO. |
| | |
| | 6) NOTE: PLEASE SHOW THE LOCATION OF ALL SERVICE |
| | EQUIPMENT ON PLANS MEETING 110.26, 240.24 PLEASE |
| | INDICATE THE EXISTING MAIN AS PART OF THE SERVICE. THE |
| | LOAD CALCULATIONS STATE *PROPOSED SERVICE* YET THE |
| | RISER SHOWS *EXISTING*? |
| | FOR EXAMPLE: PLEASE SEE THE SERVICE PANEL OUTSIDE IS |
| | SHOWN DIRECTLY BEHIND THE CONDENSING UNIT WHICH DOES |
| | NOT MEET 110.26 AND ONE OR THE TWO ARE REQUIRED TO |
| | MOVE. |
| | |
| | 7) NOTE: PLANS APPEAR TO BE MISSING A GFI RECEPTACLE |
| | ALONG KITCHEN COUNTER SPACE WITHIN 2FT OF THE END PER |
| | 210.52C1. |
| | PLEASE VERIFY AND ADJUST ON PLANS. BASED ON SCALE SHOWN |
| | THIS IS MISSING. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |