Plan Review Notes
Plan Review Notes For Permit 06091064
Permit Number 06091064
Review Stop E
Sequence Number 4
Notes
Date Text
2008-03-07 12:26:09** DENIED REVIEWFOR REVISION **
  
 ** PLEASE SEE SEVERAL ITEMS FROM ORIGINAL *PROVISO*
 GIVEN ON 5/8/07 HAVE NOT BEEN ADDRESSED.
  
 1) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 2) NOTE: PLEASE SEE MISSING REFLECTED CODES TO BE
 STATED ON PLANS.
 2005 NFPA-70
 2004 FBC W/2006 REVISIONS
 2002 NFPA-72
  
 3) NOTE: PLEASE SEE THE CIRCUITING FOR DINING ROOM
 RECEPTACLES ARE STILL SHOWING #14 AWG AND 15AMP
 BREAKERS WHEN THE CODE SPECIFICALLY REQUIRE THE MINIMUM
 OF 20AMP AND #12 AWG.
 THIS WAS REDLINED ON PREVIOUS PLANS ISSUED FOR PERMIT
 AND STILL HAS NOT BEEN CHANGED.
  
 4) NOTE: PLEASE SEE THE LOADS WHICH ARE REQUIRED TO BE
 FIGURED INTO LOAD CALCULATIONS FOR DINING ROOM CIRCUITS
 SHALL BE PER 220.52, 210.11C1 AND 210.52B1
 ** MINIMUM 1500VA FOR EACH AND THIS LOAD SHALL BE IN
 ADDITION TO ANY OTHER SMALL APPLIANCE CIRCUITS.
 ON PREVIOUS REVIEW AND REDLINED ON PLANS WITH
 PROVISO*.
  
 5) NOTE: PLEASE SEE THE REFRIGERATOR CIRCUIT WHICH
 STILL SHOWS #14 AWG WITH 20AMP BREAKER WHICH IS NOT
 PERMITTED.
 240.4, 310.16 ETC
 ** NOTED ON PREVIOUS REVIEW AND REDLINED ON PLANS ALONG
 WITH PROVISO.
  
 6) NOTE: PLEASE SHOW THE LOCATION OF ALL SERVICE
 EQUIPMENT ON PLANS MEETING 110.26, 240.24 PLEASE
 INDICATE THE EXISTING MAIN AS PART OF THE SERVICE. THE
 LOAD CALCULATIONS STATE *PROPOSED SERVICE* YET THE
 RISER SHOWS *EXISTING*?
 FOR EXAMPLE: PLEASE SEE THE SERVICE PANEL OUTSIDE IS
 SHOWN DIRECTLY BEHIND THE CONDENSING UNIT WHICH DOES
 NOT MEET 110.26 AND ONE OR THE TWO ARE REQUIRED TO
 MOVE.
  
 7) NOTE: PLANS APPEAR TO BE MISSING A GFI RECEPTACLE
 ALONG KITCHEN COUNTER SPACE WITHIN 2FT OF THE END PER
 210.52C1.
 PLEASE VERIFY AND ADJUST ON PLANS. BASED ON SCALE SHOWN
 THIS IS MISSING.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved