2008-02-22 14:49:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION TO PLANS **
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS ON FILE ARE CALLING FOR
 32,785 TOTAL COOLING BTU'S, MECHANICAL REVISION IS
 SHOWING TWO SYSTEMS TOTALING 47,600 COOLING BTU'S. THE
 PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CAL'S, SEE 2004 FBC 13-607.1.ABC.1.1. PLEASE CORRECT
 PLANS OR COOLING LOAD CAL'S.
  
 2) PLEASE SHOW THE LOCATION OF CONDENSER UNIT #2 ON
 PLAN.
  