| 2008-02-22 14:49:21 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | ** MECHANICAL REVISION TO PLANS ** | | | *** DENIED *** | | | 1) COOLING LOAD CALCULATIONS ON FILE ARE CALLING FOR | | | 32,785 TOTAL COOLING BTU'S, MECHANICAL REVISION IS | | | SHOWING TWO SYSTEMS TOTALING 47,600 COOLING BTU'S. THE | | | PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD | | | CAL'S, SEE 2004 FBC 13-607.1.ABC.1.1. PLEASE CORRECT | | | PLANS OR COOLING LOAD CAL'S. | | | | | | 2) PLEASE SHOW THE LOCATION OF CONDENSER UNIT #2 ON | | | PLAN. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|