| 2007-03-21 19:47:15 | |
| | |
| | ****** UNSAT2ND REVIEW ****** |
| | |
| | ** PLEASE SEE THERE ARE MANY ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW |
| | COMMENTS BASED ON CHANGES IN PLANS, OR NEW ITEMS SHOWN |
| | WHICH WERE NOT ON PREVIOUS PLANS. |
| | |
| | 1) NOTE: PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING |
| | RELEVANT CODES 2002 NFPA-70 (NEC), 2002 NFPA-72. SAME |
| | NOTE FROM PREVIOUS REVIEW. |
| | |
| | 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULE NOW SUBMITTED. PLEASE |
| | SEE SMOKE ALARMS WHICH ARE MISSING CIRCUITING. PLEASE |
| | BE SURE TO ALSO SEE 210.12 FOR AFCI PROTECTION |
| | REQUIRED. |
| | 310.16, 240.4, 408.4 |
| | |
| | 3) NOTE: PLEASE SEE A RISER DIAGRAM IS NOW SHOWN AND |
| | SHOWS THE SERVICE AS EXISTING, YET THE PANEL WHICH IS |
| | NOTED ON RISER IS NOT SHOWN ON PLANS FOR LOCATION. |
| | PLEASE SEE 110.26, 408.7 AND 240.24. |
| | |
| | 4)NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| | KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI |
| | PROTECTED. SAME NOTE ON PREVIOUS REVIEW. |
| | |
| | 5) NOTE: PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS |
| | REQUIRED ON THE RISER FOR THE GROUNDING ELECTRODE |
| | SYSTEM. |
| | |
| | 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR |
| | DINING ROOM. PLEASE SEE THE LOAD IS BEING SHOWN AT |
| | 1200VA. |
| | PLEASE ALSO SEE THESE SAME SECTIONS OF THE CODE AS THE |
| | LOAD FOR THE SMALL APPLIANCE CIRCUITS ARE BEING SHOWN |
| | WITH THE SAME 1200VA. |
| | NOTED ON PREVIOUS REVIEW. |
| | |
| | 7) NOTE: PLEASE SEE 210.8A1 FOR RECEPTACLES IN BATH |
| | ROOMS WHICH ARE REQUIRED TO BE GFI. |
| | PLEASE ALSO SEE EXISTING BATHROOMS. |
| | PLEASE ALSO SEE THE MISSING GFI RECEPTACLE REQUIRED IN |
| | POWDER RM. |
| | 210.52D, 210.11C1 |
| | |
| | 8) NOTE: PLEASE SEE WATER HEATER SHOWN WITHOUT THE |
| | REQUIRED DISCONNECT PER 422.30, 422.31. |
| | |
| | 9) NOTE: PLEASE SHOW LOAD CALCULATIONS FOR HOUSE PER |
| | 220.31B. |
| | SAME NOTE ON PREVIOUS REVIEW. |
| | |
| | 10) NOTE: PLEASE SEE RISER NOW SHOWS A 2-POLE BREAKER |
| | FOR GFI CIRCUIT? PLEASE ALSO SEE RISER ALSO SHOWS A |
| | 2-POLE 60AMP CIRCUIT TO POOL EQUIPMENT; HOWEVER POOL |
| | EQUIPMENT WOULD MEAN A POOL PANEL AS CIRCUITED. IF THIS |
| | IS THE CASE PLEASE INCLUDE PANEL ON RISER, FEEDERS |
| | ETC. |
| | |
| | IF THERE IS NO PANEL, THEN THIS WOULD NOT BE A 60AMP |
| | BREAKER FOR GENERAL POOL EQUIPMENT. |
| | PLEASE CLARIFY THIS INFORMATION. |
| | 240.4, 310.16, |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 11) NOTE: PLEASE SHOW THE LOCATION OF THE A/C EQUIPMENT |
| | REQUIRED DISCONNECTS PER 440.11. |
| | |
| | 12) NOTE: PLEASE SEE NOW NOTE #24 ON PLANS; THIS HAS |
| | CHANGED FROM PREVIOUS PLANS WHICH WAS NOTE #22. PLEASE |
| | SEE THIS AS IT REFERENCES CODES FROM THE 1996 NFPA-72. |
| | PLEASE SEE AT PRESENT WITH THE 2002 NFPA-72, 11.5.1.1, |
| | AND 11.8.3 IS THE CURRENT SECTIONS FOR INSTALLATIONS OF |
| | SMOKE ALARMS. PLEASE SEE PLAN NOTE MENTIONS SD'S IS |
| | SMOKE DETECTORS. PLEASE SEE PLANS NOW SHOW SA FOR SMOKE |
| | ALARMS. PLEASE SEE 11.8.3 AS THE SA SHOWN OUTSIDE |
| | BEDROOM #2 AND #3 IS SHOWN TOO CLOSE TO THE BATHROOM |
| | DOOR. MUST BE AT LEAST 3FT FROM DOOR OPENING. |
| | PART OF THIS IS STILL FROM PREVIOUS REVIEW NOTES WITH |
| | RESPECT TO OLD CODE BEING REFERENCED. |
| | |
| | 13) NOTE: PLEASE CLARIFY THE FIXTURES SHOWN IN CLOSETS |
| | TO MEET 410.8. PLEASE KNOW AN ASSUMED 12" SHELF SHALL |
| | BE DETERMINED. |
| | |
| | 14) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | |
| | 15) NOTE: PLEASE SEE THE RISER WHICH DOES NOT INCLUDE |
| | ANY EXISTING OR NEW MAIN. HOW IS THIS PANEL WHICH IS |
| | BEING NOTED AS EXISTING 200AMP PANEL BEING FED? PLEASE |
| | ELABORATE ON RISER AND PROVIDE COMPLETED INFORMATION ON |
| | RISER AS NOTED. |
| | 215.5, 230.2, 230.70, 230.71, 230.72, 240.4, 310.16 |
| | ETC. |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 16) NOTE: PLEASE SEE THE NOTICE OF COMMENCMENT WHICH |
| | WAS RECORDED IN 9/06 HAS EXPIED PER FS 713.13(2). |
| | PLEASE KNOW THAT A NEW RECORDED NOC WILL BE REQUIRED |
| | BEFORE PICKING UP PERMIT AFTER ISSUANCE. IT IS |
| | SUGGESTED THAT THE NOC DOES NOT GET RE-RECORDED UNTIL |
| | PERMIT IS ISSUED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |