2007-03-21 19:47:15 
  
 ****** UNSAT2ND REVIEW ******
  
 ** PLEASE SEE THERE ARE MANY ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS, OR NEW ITEMS SHOWN
 WHICH WERE NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING
 RELEVANT CODES 2002 NFPA-70 (NEC), 2002 NFPA-72. SAME
 NOTE FROM PREVIOUS REVIEW.
  
 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULE NOW SUBMITTED. PLEASE
 SEE SMOKE ALARMS WHICH ARE MISSING CIRCUITING. PLEASE
 BE SURE TO ALSO SEE 210.12 FOR AFCI PROTECTION
 REQUIRED.
 310.16, 240.4, 408.4
  
 3) NOTE: PLEASE SEE A RISER DIAGRAM IS NOW SHOWN AND
 SHOWS THE SERVICE AS EXISTING, YET THE PANEL WHICH IS
 NOTED ON RISER IS NOT SHOWN ON PLANS FOR LOCATION.
 PLEASE SEE 110.26, 408.7 AND 240.24.
  
 4)NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI
 PROTECTED. SAME NOTE ON PREVIOUS REVIEW.
  
 5) NOTE: PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS
 REQUIRED ON THE RISER FOR THE GROUNDING ELECTRODE
 SYSTEM.
  
 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR
 DINING ROOM. PLEASE SEE THE LOAD IS BEING SHOWN AT
 1200VA.
 PLEASE ALSO SEE THESE SAME SECTIONS OF THE CODE AS THE
 LOAD FOR THE SMALL APPLIANCE CIRCUITS ARE BEING SHOWN
 WITH THE SAME 1200VA.
 NOTED ON PREVIOUS REVIEW.
  
 7) NOTE: PLEASE SEE 210.8A1 FOR RECEPTACLES IN BATH
 ROOMS WHICH ARE REQUIRED TO BE GFI.
 PLEASE ALSO SEE EXISTING BATHROOMS.
 PLEASE ALSO SEE THE MISSING GFI RECEPTACLE REQUIRED IN
 POWDER RM.
 210.52D, 210.11C1
  
 8) NOTE: PLEASE SEE WATER HEATER SHOWN WITHOUT THE
 REQUIRED DISCONNECT PER 422.30, 422.31.
  
 9) NOTE: PLEASE SHOW LOAD CALCULATIONS FOR HOUSE PER
 220.31B.
 SAME NOTE ON PREVIOUS REVIEW.
  
 10) NOTE: PLEASE SEE RISER NOW SHOWS A 2-POLE BREAKER
 FOR GFI CIRCUIT? PLEASE ALSO SEE RISER ALSO SHOWS A
 2-POLE 60AMP CIRCUIT TO POOL EQUIPMENT; HOWEVER POOL
 EQUIPMENT WOULD MEAN A POOL PANEL AS CIRCUITED. IF THIS
 IS THE CASE PLEASE INCLUDE PANEL ON RISER, FEEDERS
 ETC.
  
 IF THERE IS NO PANEL, THEN THIS WOULD NOT BE A 60AMP
 BREAKER FOR GENERAL POOL EQUIPMENT.
 PLEASE CLARIFY THIS INFORMATION.
 240.4, 310.16,
 FBC 106.1.2, 106.3.5.4
  
 11) NOTE: PLEASE SHOW THE LOCATION OF THE A/C EQUIPMENT
 REQUIRED DISCONNECTS PER 440.11.
  
 12) NOTE: PLEASE SEE NOW NOTE #24 ON PLANS; THIS HAS
 CHANGED FROM PREVIOUS PLANS WHICH WAS NOTE #22. PLEASE
 SEE THIS AS IT REFERENCES CODES FROM THE 1996 NFPA-72.
 PLEASE SEE AT PRESENT WITH THE 2002 NFPA-72, 11.5.1.1,
 AND 11.8.3 IS THE CURRENT SECTIONS FOR INSTALLATIONS OF
 SMOKE ALARMS. PLEASE SEE PLAN NOTE MENTIONS SD'S IS
 SMOKE DETECTORS. PLEASE SEE PLANS NOW SHOW SA FOR SMOKE
 ALARMS. PLEASE SEE 11.8.3 AS THE SA SHOWN OUTSIDE
 BEDROOM #2 AND #3 IS SHOWN TOO CLOSE TO THE BATHROOM
 DOOR. MUST BE AT LEAST 3FT FROM DOOR OPENING.
 PART OF THIS IS STILL FROM PREVIOUS REVIEW NOTES WITH
 RESPECT TO OLD CODE BEING REFERENCED.
  
 13) NOTE: PLEASE CLARIFY THE FIXTURES SHOWN IN CLOSETS
 TO MEET 410.8. PLEASE KNOW AN ASSUMED 12" SHELF SHALL
 BE DETERMINED.
  
 14) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 15) NOTE: PLEASE SEE THE RISER WHICH DOES NOT INCLUDE
 ANY EXISTING OR NEW MAIN. HOW IS THIS PANEL WHICH IS
 BEING NOTED AS EXISTING 200AMP PANEL BEING FED? PLEASE
 ELABORATE ON RISER AND PROVIDE COMPLETED INFORMATION ON
 RISER AS NOTED.
 215.5, 230.2, 230.70, 230.71, 230.72, 240.4, 310.16
 ETC.
 FBC 106.1.2, 106.3.5.4
  
 16) NOTE: PLEASE SEE THE NOTICE OF COMMENCMENT WHICH
 WAS RECORDED IN 9/06 HAS EXPIED PER FS 713.13(2).
 PLEASE KNOW THAT A NEW RECORDED NOC WILL BE REQUIRED
 BEFORE PICKING UP PERMIT AFTER ISSUANCE. IT IS
 SUGGESTED THAT THE NOC DOES NOT GET RE-RECORDED UNTIL
 PERMIT IS ISSUED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]