Plan Review Notes
Plan Review Notes For Permit 06091064
Permit Number 06091064
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-16 07:50:19****** UNSAT *********
  
 1) NOTE: PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING
 RELEVANT CODES 2002 NFPA-70 (NEC), 2002 NFPA-72 .
  
 2) NOTE: PLEASE COMPLETE THE PANEL SCHEDULE INCLUDING
 ALL CONDUCTOR SIZES ALONG WITH THE OCP
 DEVICES/BREAKERS. 310.16, 240.4, 408.4
  
 3) NOTE: PLEASE SEE LOAD CALCS MENTIONS "OVENS" YET
 ONLY ONE SHOWN ON PANEL SCHEDULE AND LOAD CALCS. PLEASE
 CLARIFY AND ADJUST.
 220.31, 408.4 ETC.
  
 4)NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI
 PROTECTED.
  
 5) NOTE: PLEASE BE SUREPANEL SCHEDULE IS SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. IE: BEDRM #2
 RECEPTS, BATH RECEPTS, ETC
 408.4, 310.16, 240.4
  
 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR
 DINING ROOM.(NEW OR EXSITIGN?)
  
 7) NOTE: PLEASE SEE 210.8A1 FOR RECEPTS IN BATH RMS
 WHICH ARE REQUIRED TO BE GFI.
 PLEASE ALSO SEE EXISITING BATHRMS ARE BEING SHOWN AS
 WORK BEING IN THOSE AREAS, PLEASE SEE HOWEVER THERE ARE
 NOT GFI RECEPTS INIDCATED ON PLANS ? ARE THEY GOING TO
 BE NEW OR EXISTING.
 210.52D, 210.11C1
  
 8) NOTE: PLEASE SEE 422.17 FOR WHAT APPEARS TO BE A
 WATER HEATER IN A STORAGE CLOTHES CLOSET WHICH IS NOT
 PERMITTED.
  
 9) NOTE: PLEASE SHOW LOAD CALCULATIONS FOR HOUSE PER
 220.31B.
  
 10) NOTE: PLEASE SHOW LOCATION OF SERVICE ON PLANS.
 PANEL, METER OR MAIN?
 IF THIS GOING TO BE A NEW SERVICE PLEASE SUBMIT A
 COMPLETE RISER DIAGRAM ALONG WITH AIC RATINGS ,
 CONDUCTORS, GROUNDING ETC.
  
 11) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS ALL
 EXISTIGN BEDRMS BEING REWIRED TO CODE, HOWEVER PLEASE
 PROVIDE A LAYOUT FOR EITHER NEW OR EXISTING RECEPTS
 MEETING SPACING REQUIRMENTS PER 210.52.
  
 12) NOTE: PLEASE SHOW THE LOCATION OF THE A/C EQUIPMENT
 AND REQUIRED DISCONNECT'S PER 440.11.
  
 13) NOTE: PLEASE SHOW REQUIRED GFI PER 210.63/210.8A2
  
 14) NOTE: PLEASE SEE NOTE #22 ON PLANS AS IT REFERENCES
 CODES FROM THE 1996 NFPA-72.
 PLEASE SEE AT PRESENT WITH THE 2002 NFPA-72, 11.5.1.1,
 AND 11.8.3 ARE THE CURRENT SECTIONS FOR INSTALLATIONS
 OF SMOKE ALARMS. PLEASE SEE PLANS MENTIONS SD'S IS
 SMOKE DETECTORS. PLEASE VERIFY AS IF THESE ARE SMOKE
 DETECTORS, PLEASE VERIFY THE SYSTEM BEING INSTALLED AND
 WHAT DEVICES AND LOCATIONS FOR AUDIBLE SIGNAL WILL BE.
 PLEASE SEE DEFINITIONS AS THIS SEEMS PERHAPS THEY
 SHOULD BE SHOWN AS "SA"'S SMOKE ALARMS.
 PLEASE BE AWARE OF THE OCATIONF OF THE SD/SA SHOWN AT
 AHU LOCATION, 5'MIN AWAY FROM RA GRILLE(ONLY NOTED).
  
 15) NOTE: PLEASE SEE LOAD CALCS MENTIONS
 "FUTURELANSCAPE LTS" YET NO LOADS SHOWN?
  
 16) NOTE: PLEASE CLARFIY THE FIXTURES SHOWNIN CLOSETS
 TO MEET 410.8. PLEASE KNOW AN ASSUMNED 18" SHELF SHALL
 BE DETERMINED.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED THERE MAY BE FUTURE COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-10-15 20:58:46IN ELEC FOR REVIEW , NOTES TO FOLLOW