| 2006-10-16 07:50:19 | ****** UNSAT ********* |
| | |
| | 1) NOTE: PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING |
| | RELEVANT CODES 2002 NFPA-70 (NEC), 2002 NFPA-72 . |
| | |
| | 2) NOTE: PLEASE COMPLETE THE PANEL SCHEDULE INCLUDING |
| | ALL CONDUCTOR SIZES ALONG WITH THE OCP |
| | DEVICES/BREAKERS. 310.16, 240.4, 408.4 |
| | |
| | 3) NOTE: PLEASE SEE LOAD CALCS MENTIONS "OVENS" YET |
| | ONLY ONE SHOWN ON PANEL SCHEDULE AND LOAD CALCS. PLEASE |
| | CLARIFY AND ADJUST. |
| | 220.31, 408.4 ETC. |
| | |
| | 4)NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING |
| | KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI |
| | PROTECTED. |
| | |
| | 5) NOTE: PLEASE BE SUREPANEL SCHEDULE IS SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. IE: BEDRM #2 |
| | RECEPTS, BATH RECEPTS, ETC |
| | 408.4, 310.16, 240.4 |
| | |
| | 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR |
| | DINING ROOM.(NEW OR EXSITIGN?) |
| | |
| | 7) NOTE: PLEASE SEE 210.8A1 FOR RECEPTS IN BATH RMS |
| | WHICH ARE REQUIRED TO BE GFI. |
| | PLEASE ALSO SEE EXISITING BATHRMS ARE BEING SHOWN AS |
| | WORK BEING IN THOSE AREAS, PLEASE SEE HOWEVER THERE ARE |
| | NOT GFI RECEPTS INIDCATED ON PLANS ? ARE THEY GOING TO |
| | BE NEW OR EXISTING. |
| | 210.52D, 210.11C1 |
| | |
| | 8) NOTE: PLEASE SEE 422.17 FOR WHAT APPEARS TO BE A |
| | WATER HEATER IN A STORAGE CLOTHES CLOSET WHICH IS NOT |
| | PERMITTED. |
| | |
| | 9) NOTE: PLEASE SHOW LOAD CALCULATIONS FOR HOUSE PER |
| | 220.31B. |
| | |
| | 10) NOTE: PLEASE SHOW LOCATION OF SERVICE ON PLANS. |
| | PANEL, METER OR MAIN? |
| | IF THIS GOING TO BE A NEW SERVICE PLEASE SUBMIT A |
| | COMPLETE RISER DIAGRAM ALONG WITH AIC RATINGS , |
| | CONDUCTORS, GROUNDING ETC. |
| | |
| | 11) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS ALL |
| | EXISTIGN BEDRMS BEING REWIRED TO CODE, HOWEVER PLEASE |
| | PROVIDE A LAYOUT FOR EITHER NEW OR EXISTING RECEPTS |
| | MEETING SPACING REQUIRMENTS PER 210.52. |
| | |
| | 12) NOTE: PLEASE SHOW THE LOCATION OF THE A/C EQUIPMENT |
| | AND REQUIRED DISCONNECT'S PER 440.11. |
| | |
| | 13) NOTE: PLEASE SHOW REQUIRED GFI PER 210.63/210.8A2 |
| | |
| | 14) NOTE: PLEASE SEE NOTE #22 ON PLANS AS IT REFERENCES |
| | CODES FROM THE 1996 NFPA-72. |
| | PLEASE SEE AT PRESENT WITH THE 2002 NFPA-72, 11.5.1.1, |
| | AND 11.8.3 ARE THE CURRENT SECTIONS FOR INSTALLATIONS |
| | OF SMOKE ALARMS. PLEASE SEE PLANS MENTIONS SD'S IS |
| | SMOKE DETECTORS. PLEASE VERIFY AS IF THESE ARE SMOKE |
| | DETECTORS, PLEASE VERIFY THE SYSTEM BEING INSTALLED AND |
| | WHAT DEVICES AND LOCATIONS FOR AUDIBLE SIGNAL WILL BE. |
| | PLEASE SEE DEFINITIONS AS THIS SEEMS PERHAPS THEY |
| | SHOULD BE SHOWN AS "SA"'S SMOKE ALARMS. |
| | PLEASE BE AWARE OF THE OCATIONF OF THE SD/SA SHOWN AT |
| | AHU LOCATION, 5'MIN AWAY FROM RA GRILLE(ONLY NOTED). |
| | |
| | 15) NOTE: PLEASE SEE LOAD CALCS MENTIONS |
| | "FUTURELANSCAPE LTS" YET NO LOADS SHOWN? |
| | |
| | 16) NOTE: PLEASE CLARFIY THE FIXTURES SHOWNIN CLOSETS |
| | TO MEET 410.8. PLEASE KNOW AN ASSUMNED 18" SHELF SHALL |
| | BE DETERMINED. |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED THERE MAY BE FUTURE COMMENTS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2006-10-15 20:58:46 | IN ELEC FOR REVIEW , NOTES TO FOLLOW |