| 2006-10-24 13:11:27 | DENIED |
| | |
| | |
| | 1.SUBMIT TWO ORIGINAL SIGNED AND SEALED SURVEYS.FS |
| | 472.025 |
| | |
| | 2.SHOW THE TYPE OF LAP SIDING USED. |
| | |
| | 3.SHOW ROOF SHEATHING NAILING SCHEDULE.FBC 2304.9.1 |
| | TABLE 31 |
| | |
| | 4.SUBMIT TWO COPIES OF ENERGY CALCS PER 2004 FBC. |
| | |
| | 5.DOOR STATE PRODUCT APPROVAL MISSING EVALUATION |
| | REPORT.ROOF PRODUCT APPROVAL MISSING STATE PRODUCT |
| | APPROVAL.ALL PRODUCT APPROVALS SUBMITTED WITH |
| | QUALITY ASSURANCE SHALL HAVE THE FOLLOWING STATE |
| | APPROVAL ATTACHED. |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF |
| | THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN |
| | APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC |
| | FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 6.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3. |
| | |
| | |
| | 7.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER |
| | 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE |
| | APPROVED PRIOR TO INSTALLATION. |
| | |
| | 8.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR |
| | A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS |
| | WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC |
| | EXISTING BUILDING 301.5 |
| | |
| | 9.R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS |
| | TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| | GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM |
| | OF 6 INCHESWITHIN THE FIRST 10 FEET. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE |
| | COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | |
| | |