| Plan Review Notes For Permit 06091063 |
| Permit Number |
06091063 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-30 10:36:54 | BUILDING REVIEW 2ND CHECKLIST: | | | | | | 1-PRODUCT APPROVAL FL6968 FOR CLEAR BERTHA STORM | | | PANELS DOESN'T WORK FOR OPENING #2.OPENING IS 328" X | | | 156".SEE TABLE ON SHEET 3 OF 4 OF DRAWINGS NO 05-276 | | | SUBMITTED FOR MAXIMUM PANEL LENGTH ALLOWED ACCORDING TO | | | THE DESIGN PRESSURES.NEED TO PROVIDE PRODUCT APPROVAL | | | FOR STORM PANELS THAT WILL WORK FOR OPENING #2. | | | | | | 2- PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED | | | CITY SAMPLE.PROVIDE ALL REQUIRED INFORMATION TO | | | VERIFY COMPLIANCE WITH PRODUCT APPROVAL PROPOSED | | | INSTALLATION. SEE TABLE 1609.6B FBC 2004 TO DETERMINE | | | THE OPENING DESIGN PRESSURES. SEE ATTACHED COPY. SEC. | | | 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|