| Plan Review Notes For Permit 06091050 |
| Permit Number |
06091050 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-19 13:21:06 | *****UNSAT***** | | | | | | | | | | | | | | | 1.)SINCE THE CONTRACT IS GREATER THAN $5000.00, THE | | | DOCUMENTS WILL REQUIRE AN ENGINEER'S SEAL THAT HAS BEEN | | | SIGNED, DATED, AND STAMPED AS PROVIDED IN SECTION | | | 471.025, FLORIDA STATUTES. | | | | | | 2.)AS PER WPB FIRE PREVENTION, DUCT SMOKE DETECTORS | | | SHALL INTIATE A GENERAL ALARM. | | | | | | 3.)WATERFLOW TO ACTIVATE GENERAL ALARM WITHIN 45 TO | | | 60 SECONDS. | | | | | | 4.)THE SILENCING OF THE FIRE ALARM SYSTEM SHALL IN NO | | | WAY DEACTIVATE VISUAL/STROBE DEVICES. | | | | | | 5.)UL CERTIFICATE FOR CENTAL STATION SERVICE TO BE AT | | | THE FACP AND A COPY SUBMITTED TO WPB FIRE PREVENTION BY | | | FINAL FIRE ALARM INSPECTION. | | | | | | 6.)COORDINATE WITH THE GENERAL CONTRACTOR AND/OR THE | | | SPRINKLER CONTRACTOR THAT THE DOUBLE DETECTOR CHECK | | | VALVE BE CHAINED AND LOCKED AT THE COMPLETION OF FIRE | | | ALARM/SPRINKLER FINAL. | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|