Plan Review Notes
Plan Review Notes For Permit 06091050
Permit Number 06091050
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-19 13:21:06*****UNSAT*****
  
  
  
  
 1.)SINCE THE CONTRACT IS GREATER THAN $5000.00, THE
 DOCUMENTS WILL REQUIRE AN ENGINEER'S SEAL THAT HAS BEEN
 SIGNED, DATED, AND STAMPED AS PROVIDED IN SECTION
 471.025, FLORIDA STATUTES.
  
 2.)AS PER WPB FIRE PREVENTION, DUCT SMOKE DETECTORS
 SHALL INTIATE A GENERAL ALARM.
  
 3.)WATERFLOW TO ACTIVATE GENERAL ALARM WITHIN 45 TO
 60 SECONDS.
  
 4.)THE SILENCING OF THE FIRE ALARM SYSTEM SHALL IN NO
 WAY DEACTIVATE VISUAL/STROBE DEVICES.
  
 5.)UL CERTIFICATE FOR CENTAL STATION SERVICE TO BE AT
 THE FACP AND A COPY SUBMITTED TO WPB FIRE PREVENTION BY
 FINAL FIRE ALARM INSPECTION.
  
 6.)COORDINATE WITH THE GENERAL CONTRACTOR AND/OR THE
 SPRINKLER CONTRACTOR THAT THE DOUBLE DETECTOR CHECK
 VALVE BE CHAINED AND LOCKED AT THE COMPLETION OF FIRE
 ALARM/SPRINKLER FINAL.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722