| Plan Review Notes For Permit 06091017 |
| Permit Number |
06091017 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-12 15:05:45 | ***PROVISO*** | | | | | | THESE PLANS APPEAR TO BE CODE COMPLIANT HOWEVER PLEASE | | | NOTE THE FOLLOWING: | | | | | | 1) THE VISUAL DEVICE IN THE CORRIDOR SOUTH OF STAIR #1 | | | IS LOCATED ON A WALL THAT WOULD APPEAR TO BE DIFFICULT | | | TO VISUALIZE WHILE IN THAT CORRIDOR. SHT FA 2.1. | | | | | | 2) PLEASE ENSURE THAT THE REQUIRED AUDIBILITY WILL BE | | | ACHIEVED IN CORRIDOR 807 WITH A STROBE ONLY. SHT FA | | | 2.2. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 |
|