| 2006-10-17 20:10:19 | ******UNSAT *********** | | | | | | 1) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL WIRING | | | DETAIL SHOWING THE CONDUCTORS, CONDUITS , OCP DEVICES | | | ETC FOR THE EQUIPMENT SCHEDULE WHICH IS BEING SHOWN. | | | THE DISCONNECTS ON SHEETSP 201 ARE NOT COMPLETE AT | | | THIS TIME FOR REVIEW. | | | PLEASE ALSO ONLY SUBMIT THE PANEL SCHEDULE WHICH FEEDS | | | THIS EQUIPMENT FOR THE ABOVE. | | | 240.4,310.16, 680.20, 215.5, 215.3,230.42 ETC. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|