| 2006-11-07 16:51:31 | DENIED BY BUILDING |
| | |
| | 1)THREE SETS OF SIGNED AND SEALED PLANS FOR THE POOL |
| | AND SPA ARE REQUIRED TO BE SUBMITTED WITH THE PERMIT |
| | APPLICATION (# 06091005). |
| | |
| | BASED ON A REVIEW OF OUR FILE SET OF PLANS THAT WERE |
| | SUBMITTED FOR THE POOL PLUMBING PERMIT (# 06071766) |
| | PLEASE SEE THE FOLLOWING COMMENTS: |
| | |
| | 2)SOME OF THE DETAIL TAGS ON SHEET SP-104 LIST THE |
| | WRONG PAGE NUMBER. PLEASE CORRECT. |
| | |
| | 3) ON SP-1.05 THE DETAIL TAG FOR THE POOL LADDER LISTS |
| | THE WRONG PAGE NUMBER. |
| | |
| | 4) ON SP-2.02 THE DETAIL TAG FOR THE ANCHOR SOCKET |
| | DETAIL HAS THE WRONG DETAIL NUMBER AND PAGE NUMBER. |
| | |
| | 5) 13-412.1.ABC.2.6.1 TIME SWITCHES. |
| | TIME SWITCHES SHALL BE INSTALLED ON SWIMMING POOL |
| | HEATERS AND PUMPS. |
| | EXCEPTIONS: |
| | 1.WHERE PUBLIC HEALTH STANDARDS REQUIRE |
| | 24-HOUR PUMP OPERATION. |
| | 2.WHERE PUMPS ARE REQUIRED TO OPERATE SOLAR |
| | AND WASTE HEAT RECOVERY POOL HEATING SYSTEMS. |
| | |
| | 6) 13-412.1.ABC.2.6.2 POOL COVERS. |
| | HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT |
| | POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO |
| | MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A |
| | MINIMUM INSULATION VALUE OF R -12. |
| | EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY |
| | FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY |
| | SOURCE. |
| | |
| | 7) 13-412.1.ABC.2.6.3 POOL HEATERS. |
| | POOL HEATERS SHALL BE EQUIPPED WITH A READILY |
| | ACCESSIBLE ON-OFF SWITCH TO ALLOW SHUTTING OFF THE |
| | HEATER WITHOUT ADJUSTING THE THERMOSTAT SETTING. POOL |
| | HEATERS FIRED BY NATURAL GAS SHALL NOT HAVE |
| | CONTINUOUSLY BURNING PILOT LIGHTS. |
| | |