Plan Review Notes For Permit 06091005
Permit Number 06091005
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-07 16:51:31DENIED BY BUILDING
  
 1)THREE SETS OF SIGNED AND SEALED PLANS FOR THE POOL
 AND SPA ARE REQUIRED TO BE SUBMITTED WITH THE PERMIT
 APPLICATION (# 06091005).
  
 BASED ON A REVIEW OF OUR FILE SET OF PLANS THAT WERE
 SUBMITTED FOR THE POOL PLUMBING PERMIT (# 06071766)
 PLEASE SEE THE FOLLOWING COMMENTS:
  
 2)SOME OF THE DETAIL TAGS ON SHEET SP-104 LIST THE
 WRONG PAGE NUMBER. PLEASE CORRECT.
  
 3) ON SP-1.05 THE DETAIL TAG FOR THE POOL LADDER LISTS
 THE WRONG PAGE NUMBER.
  
 4) ON SP-2.02 THE DETAIL TAG FOR THE ANCHOR SOCKET
 DETAIL HAS THE WRONG DETAIL NUMBER AND PAGE NUMBER.
  
 5) 13-412.1.ABC.2.6.1 TIME SWITCHES.
 TIME SWITCHES SHALL BE INSTALLED ON SWIMMING POOL
 HEATERS AND PUMPS.
 EXCEPTIONS:
 1.WHERE PUBLIC HEALTH STANDARDS REQUIRE
 24-HOUR PUMP OPERATION.
 2.WHERE PUMPS ARE REQUIRED TO OPERATE SOLAR
 AND WASTE HEAT RECOVERY POOL HEATING SYSTEMS.
  
 6) 13-412.1.ABC.2.6.2 POOL COVERS.
 HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT
 POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO
 MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A
 MINIMUM INSULATION VALUE OF R -12.
 EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY
 FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY
 SOURCE.
  
 7) 13-412.1.ABC.2.6.3 POOL HEATERS.
 POOL HEATERS SHALL BE EQUIPPED WITH A READILY
 ACCESSIBLE ON-OFF SWITCH TO ALLOW SHUTTING OFF THE
 HEATER WITHOUT ADJUSTING THE THERMOSTAT SETTING. POOL
 HEATERS FIRED BY NATURAL GAS SHALL NOT HAVE
 CONTINUOUSLY BURNING PILOT LIGHTS.
  