| Date |
Text |
| 2006-10-04 00:00:00 | ******UNSAT****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | NFPA-2004 CHAPTER 58 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PLAN REVIEW ON THE ISOMETRIC |
| | DRAWING: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED ABOVE AND BELOW GROUND, ALL |
| | PIPE SIZES, (AND THE EDH NUMBER OF |
| | CORRUGATED STAINLESS STEEL TUBING FOR |
| | EACH PIPE SIZE BEING USED. |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE |
| | (GENERATOR) AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE FBC-2004 FUEL |
| | GAS CODE SECS. 401.8 THRU 402.6.1 AND |
| | TABLES 402.4(1) THRU 402.4(33). |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | PROPANE 10 PSI. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT (1ST AND 2ND STAGE REGULATORS) |
| | TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND THE FBC-2004 FUEL GAS |
| | CODE SEC 402.2. |
| | |
| | 10. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | NOTE: THE U/G PROPANE TANK LOCATION WITH |
| | THE SET BACKS INDICATED ON THE SITE |
| | SURVEY PLAN. FRONT PROPERTY LINE IS 12', |
| | TANK DIAMETER IS 37", FRONT PROPERTY |
| | LINE TO BUILDING IS 18'-10", BY DOING |
| | THE MATH THAT LEAVES 3'-9" FROM THE SIDE |
| | OF THE TANK TO THE BUILDING. A MINIMUM |
| | OF 10' CLEARANCE IS REQUIRED FROM |
| | BUILDING TO TANK. |
| | |
| | 11. FBC-2004 CHAPTER 1,SECTION |
| | 106.3.4.2: THE PERSON RESPONSIBLE FOR |
| | THE DESIGN OF THE DRAWING SHALL CLEARLY |
| | PRINT AND SIGN NAME, AND ALSO DATE |
| | DRAWING. PLEASE DO THIS PRIOR TO |
| | RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |