2007-04-25 13:34:29 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. (#6CU MIN)
  
 3} INDICATE THE SIZE AND NUMBER OF SERVICE CONDUCTORS
 FROM THE METER TO THE DISCONNECT
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.