| Plan Review Notes For Permit 06090927 |
| Permit Number |
06090927 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-25 13:34:29 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED | | | FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER | | | 250.118, SIZED PER 250.122. | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH | | | 250.66. (#6CU MIN) | | | | | | 3} INDICATE THE SIZE AND NUMBER OF SERVICE CONDUCTORS | | | FROM THE METER TO THE DISCONNECT | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|