Plan Review Notes
Plan Review Notes For Permit 06090927
Permit Number 06090927
Review Stop B
Sequence Number 2
Notes
Date Text
2007-05-02 15:17:26BUILDING REVIEW SECOND CHECKLIST (PLAN REVIEW ONLY):
  
 1- WHEN APPLYING FOR PERMIT WILL NEED:
 A) RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 ***NOTE:PROVIDECOMPLETE ADDRESS ON TOP OF FORM AND
 LEGAL PAPER NEED TO BE NOTARIZED ALSO.
  
 B) IMPACT FEES PAID. BRING PLANS TO PALM BEACH
 COUNTY. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT.
  
 C) PAY PERMIT FEES ACCORDINGLY.
  
 2- ENERGY CALCULATIONS:
 A) NEED TO USE REVISED FORM 600A-2004R
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP
 OF FORM. EG: SPECIFY OWNER AND CONTRACTOR.
  
 C) REVISE CEILING TYPES INFORMATION ON ITEM #10.
 WHERE IS THE SINGLE ASSEMBLY LOCATED AT?. SEE PLANS.
 ALSO, REVISE THE UNDERATTIC AREA. SEE PLANS AND SEC.
 13-604.1.A.1 OF 2004 FBC.
  
 D) COMPLETE BOTTOM OF FORM. NEED PREPARER'S NAME AND
 DATE AND OWNER/AGENT NAME AND DATE.
  
 3- SURVEY DOESN'T MATCH SITE PLAN AND FLOOR PLANS.
 REVISE AS REQUIRED.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FIXED WINDOWS. DRAWINGS ARE NOT LEGIBLE.
  
 B) PRECAST LINTELS: WHY DID ARCHITECT APPROVED NOA
 03-0605.04 IF IT DOESN'T APPLY TO THIS JOB. THIS NOA IS
 FOR 4", 6" AND 12" PRECAST LINTELSONLY,WHILE
 LINTELS SPECIFIED ON PLANS ARE 8".
  
 C) ALL SIMPSON AND USP STRUCTURAL CONNECTORS
 SPECIFIEDON PLANS AND DETAILS. ONLY PRODUCT APPROVAL
 FOR SIMPSON HETA 16 AND LTA1 WERE SUBMITTED.
  
 5- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 ***NOTE:TO AVOID DENIALS AND UNNECESSARYDELAYS
 PLEASE MAKE SURE ALL PRODUCT APPROVALS ARE STAMPED AND
 ALSO MAKE SURE NAME OF ARCHITECT REVIEWING THE PRODUCT
 APPROVALS IS CLEARLY IDENTIFIED IN THE REVIEW STAMP.
  
 6- ARCHITECT TO PROVIDE THE FIRM'S NUMBER IN THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 7- SOIL TEST REPORT:
 A) BOTH COPIES TO HAVE ORIGINAL SEAL, SIGNATURE AND
 DATEAND
  
 B) BOTH COPIES TO HAVE ENGINEERING FIRM CERTIFICATE
 OF AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDAADMINISTRATIVE CODE.
  
 8- GARAGE DOOR STRUCTURAL BUCK DETAIL CALLS FOR POURED
 CONCRETE COLUMNS. PLANS CALL FOR FILLED CELLS. REVISE
 AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- SHEET A3:
 A) PROVIDE COMPLETE CALCULATIONS SHOWING HOW ALL
 DESIGN PRESSURES WERE CALCULATED. OTHERWISE, REVISE ALL
 DESIGN PRESSURES AS REQUIRED BY REVISED TABLE
 1609.6.2.1(2) OF 2004 FBC.
  
 B) ROOF LOADS DON'T MATCH ROOF LOADS SHOWN ON SHEET
 S-2. REVISE AS REQUIRED.
  
 ***NOTE: ALSO,NEED TO SPECIFY ALL LIVE AND DEAD LOADS
 AS REQUIRED BY SEC. R301 AND TABLE R301.5 OF 2004
 FLORIDA RESIDENTIALCODE.
 ALSO, INFORMATION ON SHEET A-3 AND S-2 NEED TO MATCH.
  
 10- SHEET S-1:
 A) SEE SOIL TEST REPORT AND UPDATE ALL GENERAL NOTES
 AS REQUIRED. SEE TYPE OF SOIL, ETC.
  
 B) UPDATE ALL GENERAL NOTES. SEE 2004 FLORIDA
 RESIDENTIAL CODE AND 2004 FBC FOR CORRECT REFERENCE
 STANDARD AND CORRECT YEAR TO BE REFERENCED AND REVISE
 ALL NOTES AS REQUIRED.
 SEC.106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) DROP AND EDGE FOOTING AT GARAGE AREA IS NOT DRAWN
 CORRECTLY.REVISE AS REQUIRED.
  
 11- SHEET S-2:
 A) GABLE END DETAIL. PROVIDE SPECIFIC SPECS FOR TYPE
 OF CONNECTOR TO BE INSTALLED.1" STRAP IS NOT ENOUGH
 INFORMATION TO PROVIDE PRODUCT APPROVAL.
  
 B) REVISE ROOF LOADS TO MATCH SHEET A-3. SEE COMMENT
 9(B) ABOVE.
  
 C) NAILING ZONE PLAN IS MISSING ZONE 3. REVISE AS
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 D) PROVIDE COMPLETE SPECIFICATION'S FOR ROOF
 SHEATHING FASTENING. SEE SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE FOR MINIMUM FASTENER SIZE,
 TYPE AND SPACING TO BE USED.
  
 E) CONNECTION SCHEDULE:
 * SEE CURRENT SIMPSON AND USP CATALOG AND SPECIFY ALL
 LOADS, NUMBER AND TYPE OF FASTENERS. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS TO JUSTIFY DIFFERENCE ON
 SPECSTHAT DIFFER FROM THOSE TESTED AND PUBLISHED BY
 THE MANUFACTURER.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 ** WHERE IS SIMPSON HVS26 TAKEN FROM?. UNABLE TO FIND
 IN SIMPSON CATALOG.
  
 F) SIZE OF SOFFIT VENT DOESN'T MATCH SIZE SHOWN ON
 TYP. WALL SECTION. REVISE AS REQUIRED.
  
 G) SPECIFY TRUSS CONNECTORS AT THE END OF TRUSS
 GIRDERS BY THE ENTRY AREA. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 H) SPECIFY TRUSS CONNECTOR FOR TRUSSES THAT ARE
 RESTING ON THE DOUBLE PT LEDGER BY ENTRY AREA. DETAIL
 PROVIDED IS NOT LEGIBLE. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
  
 12- STORM SHUTTERS:
 A) CLARIFY WHY ARCHITECT APPROVED PRODUCT APPROVAL
 SUBMITTED IF THERE ARE NOT DRAWINGS TO REVIEWTO
 VERIFY APPLICATION.
  
 B) PROVIDE COMPLETE DRAWINGS TO VERIFY COMPLIANCE OF
 PRODUCT PROPOSED INSTALLATION.
  
 C)INSTALLATION SCHEDULE CAN'TBE REVIEWED UNTIL
 DRAWINGS ARE SUBMITTED. BUT,INSTALLATION SCHEDULE
 NEEDS TO BE REVISED ANYWAY. EG: OPENING #2 SHOWS 26
 1/2" X 26" OPENING. THE TOTAL SHUTTER SPAN IS 31" AND
 THE MINIMUM EDGE DISTANCE IS 3 1/2".PROPOSED
 INSTALLATION DOESN'T WORK. CHECK AND REVISE COMPLETE
 INSTALLATION SCHEDULE AS REQUIRED.
  
 13- PROVIDE STRUCTURAL BUCK DETAIL FOR 2X BUCK AS
 REQUIRED BY ENTRY DOOR PRODUCT APPROVAL. SEE SEC.
 R613.6.2 OF 2004 FLORIDA RESIDENTIAL CODE FOR PROPER
 WAY OF INSTALLING BUCK AND PROVIDE DETAIL AS REQUIRED.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712