Text |
| 2006-10-06 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ARCHITECTS SIGNATURE IS A | | | PHOTOCOPY. WHEN SUBMITTING FOR | | | PERMITTING THE SIGNATURE MUST BE WET PER | | | 481.221(1)(A)FLORIDA STATUTES. | | | | | | 2} THE DISCONNECTING MEANS MUST COMPLY | | | WITH 230.70: | | | MEANS SHALL BE PROVIDED TO DISCONNECT | | | ALL CONDUCTORS IN A BUILDING OR OTHER | | | STRUCTURE FROM THE SERVICE-ENTRANCE | | | CONDUCTORS. THE MLO PANEL MUST HAVE A | | | MAIN DISCONNECT TO COMPLY. | | | | | | 11.8.3.5 SPECIFIC LOCATION REQUIREMENTS. | | | | | | (5) SMOKE ALARMS AND SMOKE DETECTORS | | | SHALL NOT BE INSTALLED WITHIN A 914-MM | | | (36-IN.) HORIZONTAL PATH FROM A DOOR TO | | | A KITCHEN OR A BATHROOM CONTAINING A | | | SHOWER OR TUB. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6676 |
|