 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ARCHITECTS SIGNATURE IS A
 PHOTOCOPY. WHEN SUBMITTING FOR
 PERMITTING THE SIGNATURE MUST BE WET PER
 481.221(1)(A)FLORIDA STATUTES.
  
 2} THE DISCONNECTING MEANS MUST COMPLY
 WITH 230.70:
 MEANS SHALL BE PROVIDED TO DISCONNECT
 ALL CONDUCTORS IN A BUILDING OR OTHER
 STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS. THE MLO PANEL MUST HAVE A
 MAIN DISCONNECT TO COMPLY.
  
 11.8.3.5 SPECIFIC LOCATION REQUIREMENTS.
  
 (5) SMOKE ALARMS AND SMOKE DETECTORS
 SHALL NOT BE INSTALLED WITHIN A 914-MM
 (36-IN.) HORIZONTAL PATH FROM A DOOR TO
 A KITCHEN OR A BATHROOM CONTAINING A
 SHOWER OR TUB.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.