2006-10-11 18:19:43BUILDING REVIEW CHECKLIST (PLAN REVIEW ONLY):
  
 1- WHEN APPLYING FOR PERMIT WILL NEED:
 A) RECORDED NOTICE OF COMMENCEMENT.
 B) IMPACT FEES PAID TO PALM BEACH COUNTY. NEED COPY
 OF PAID RECEIPT AND STAMPED PLANS.
 C) PAY PERMIT FEES ACCORDINGLY.
  
 2- NEED ENERGY CALCULATIONS AS REQUIRED BY CHAPTER 13
 FBC 2004.
  
 3- BOTH COPIES OF SURVEYS NEED TO HAVE ORIGINAL SEAL,
 SIGNATURE AND DATE AS REQUIRED BY CHAPTER 472 FLORIDA
 STATUTES.
  
 4- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) SINGLE HUNG WINDOWS.
 B) FIXED WINDOWS.
 C) ENTRY DOOR ASSEMBLY AS SHOWN ON PLANS AND
 ELEVATIONS.
 D) GARAGE DOOR.
 E) SLIDING GLASS DOORS.
 F) ALL SIMPSON AND USP CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 G) PRECAST LINTELS.
 H) ROOF SHINGLES.
  
 5- ARCHITECT TO REVIEW AND APPROVE IN WRITTING ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. INCLUDING THE STORM SHUTTERS.
  
 6-A) ARCHITECT TO PROVIDE ORIGINAL SIGNATURE IN ALL
 DRAWINGS AS REQUIRED BY CHAPTER 481 FLORIDA STATUTES
 AND CLARIFY WHY THERE ARE DRAWINGS WITH DIFFERENT
 SIGNATURES.
 B) ARCHITECT TO PROVIDE ALL INFORMATION REQUIRED BY
 FAC SEC. 61G1-16.004 IN THE TITLE BLOCK. SEE ATTACHED
 COPY.
  
 7- SURVEY AND ARCHITECT'S PLANS DON'T MATCH. REVISE AS
 REQUIRED.
  
 8- SPECIFY SAFETY GLASS FOR WINDOW NEXT TO ENTRY DOOR
 AND BY THE BATHROOM BATHTUB AS REQUIRED BY SEC. R308.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 9-REVISE SPECIFICATIONS FOR GARAGE DOOR LEADING TO
 THE INSIDE OF THE HOUSE. NEEDTO COMPLY WITH SEC.
 R309.1 2004 FLORIDA RESIDENTIAL CODE.
  
 10- SPECIFY SIZE OF WINDOW FOR MASTER BEDROOM. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 11- PROVIDE SOIL TEST REPORT.
  
 12-REVISE SITE PLAN.PROVIDE DRAINAGE PLAN SHOWING
 HOW IS WATER DIVERTED AWAY FROM THE STRUCTURE AND NO
 LEADING TO NEIGHBORS'S PROPERTY. SEC. R401.3 2004
 FLORIDA RESIDENTIAL CODE.
  
 13- SPECIFY ACTUAL SIZE OF ENTRY DOOR. NEED TO VERIFY
 COMPLIANCE WITH SEC. R311.4.2 2004 FLORIDA RESIDENTIAL
 CODE.
  
 14- PROVIDE GARAGE DOOR STRUCTURAL BUCK DETAIL. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15- CLARIFY SPECIFICATIONS FOR GABLE END SHEATHING.
 SPECS SHOWN ON ELEVATIONS (SHEET A-3) DON'T MATCH SPECS
 SHOWN ON GABLE END SECTION (SHEET S-2). REVISE AS
 REQUIRED.
  
 16- SHEET A-3:
 A) PROVIDE CALCULATIONS SHOWING HOW THE DESIGN
 PRESSURES WERE DETERMINED. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.PRESSURES ARE LOWER THAN THOSE SHOWN IN
 ASCE-02 TABLES.
 B) ROOF LOADS DON'T MATCH ROOF LOADS SHOWN ON SHEET
 S-2. REVISE AS REQUIRED.
  
 17-SHEET S-1: UPDATE ALL STRUCTURAL GENERAL NOTES.
 SEE 2004 FLORIDA RESIDENTIAL CODE AND 2004 FLORIDA
 BUILDING CODE FOR CORRECT REFERENCE STANDARDS USED AND
 SPECIFIC EDITIONS.
  
 18- SHEET S-2:
 A) GABLE END SECTION DETAIL:(1) REVISE CONNECTOR
 USP RT24F. NEED TO SPECIFY MASONRY CONNECTOR. SEE
 CATALOGUE FOR PROPER CONNECTORS.
 (2)SPECIFY SILL PLATE FOR 2X6 STUDS AND SPECIFY
 HOW IS IT FASTENED. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 B) REVISE ROOF LOADS TO INCLUDE THE ATTIC LOADS AS
 REQUIRED BY TABLE R301.5 2004 FLORIDA RESIDENTIAL
 CODE.
 C) NAILING ZONE PLAN IS MISSING ZONE #3. SEE FIGURE
 R301.1.2(8) 2004 FLORIDA RESIDENTIAL CODE.
 D) NAILING ZONE PLAN DOESN'T PROVIDE ANY SPECS FOR
 SHEATHING FASTENING. SPECIFY.
 E) CLARIFY IF USING TWO BOND BEAMS OR ONE. BEAM
 SCHEDULE CALLS FOR ONE, WHILE TYP. WALL SECTION SHOWS
 TWO.CLARIFY.
 F) CONNECTION SCHEDULE: SEE CURRENT USP AND SIMPSON
 CATALOGUES AND REVISE NUMBER AND SIZE OF NAILS USED.
 OTHERWISE, COMPLETE ENGINEERING ANALYSIS IS REQUIRED
 FOR NAIL SIZE AND NUMBER THAT DIFFER FROM THE ONE
 TESTED AND PUBLISHED BY THE MANUFACTURER.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 G) SIZE OF SOFFIT VENTS DOESN'T MATCH SIZE SHOWN ON
 TYP. WALL SECTION. REVISE AS REQUIRED.
 H) SPECIFY TRUSS CONNECTORS AT THE END OF TRUSS
 GIRDERS BY THE ENTRY AREA. SEE COMMENTS ON PLANS.
 I) SPECIFY TRUSS CONNECTORS FOR TRUSSES THAT ARE
 RESTING ON THE DOUBLE PT LEDGER BY ENTRY AREA.
  
 19- TRUSS DRAWINGS WILL BE REQUIRED PRIOR TO
 INSTALLATION AS REQUIRED BY SEC. R802.10. 2004 FLORIDA
 RESIDENTIAL CODE.
  
 20- NEED TO PROVIDE BATHROOM WITH DOOR THAT ALLOWS MIN.
 29" CLEAR OPENING AS REQUIRED BY SEC. R22 2004 FLORIDA
 RESIDENTIAL CODE.
  
 21- IF NOT USING DOOR AND WINDOWS WITH IMPACT GLAZING,
 THEN NEED TO PROVIDE COMPLETE INFORMATION FOR SHUTTERS.
 NEED PRODUCT APPROVAL, KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE OF
 INSTALLATION SCHEDULE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712