| Date |
Text |
| 2007-02-11 11:43:57 | **** UNSAT 3RD REVIEW **** |
| | |
| | *** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH |
| | ARE IN NEED OF ADDRESSING AND SOME NEW NOTES DUE TO THE |
| | PLANS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE THE SCOPE OF WORK OR NOT CLEAR AT |
| | THIS TIME. PLEASE SEE THE PREVIOUS REVIEW NOTES |
| | MENTIONED TO SUPPLY A PANEL SCHEDULE FOR NEW OR |
| | EXISTING CIRCUITS BEING DONE IN SCOPE OR EXISTING. |
| | PLEASE SEE THE PANEL SCHEDULE WHICH IS NOW BEING |
| | SUBMITTED MENTIONS ALL THE NEW CIRCUITS, HOWEVER PLEASE |
| | SEE THE PLANS DO NOT INDICATE ANY CIRCUITS FOR THESE |
| | NEW ITEMS. |
| | PLEASE SEE NOTES ON PLANS MENTIONS ALL CEILING GRID AND |
| | TILES BEING REMOVED, YET CEILING MOUNTED CEILING GRID |
| | FIXTURES ARE TO REMAIN?? PLEASE CLARIFY HOW THESE |
| | EXISTING FIXTURES ARE GOING TO BE USED. SOME ARE NOTED |
| | AS BEING NEW INDUSTRIAL TYPE FIXTURES. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EM/EXT LTS. |
| | PLEASE CLARIFY THE NEW SCOPE. |
| | PLEASE SEE ANY NEW ELECTRICAL WORK IS TO MEET THE NEW |
| | CODES FOR THAT SCOPE OF WORK. THIS IS PERMITTED UNDER |
| | THE 2002 NEC. |
| | |
| | |
| | 2) NOTE: PLEASE STATE AND DESIGN TO ALL OF THE |
| | FOLLOWING MINIMUM CODES AT A MINIMUM FOR ELECTRICAL |
| | REVIEW. |
| | NFPA-70 2002, 2003 NFPA-101, 2004 FBC. |
| | |
| | 3) NOTE: PLEASE SEE 600.5 AS THE AMPERAGE SHOWN FOR |
| | SIGN CIRCUIT IS 6AMPS WHICH DOES NOT MEET THE MINIMUM |
| | REQUIRED PER 600.5, AND 220.3(B)(6). |
| | |
| | 4) NOTE: PLEASE SEE THE SEAL WHICH IS PLACED ON |
| | ELECTRICAL PLANS IS NO LONGER VALID TO BE USED IN THE |
| | STATE OF FLORIDA. |
| | PLEASE SEE RULE 61G15-23.001 WHICH WAS CHANGED IN FEB |
| | 2004 WHICH REQUIRED ALL SEALS BY ENGINEERS TO USE THE |
| | NEW WORDING OF LICENSE. THE TIME WAS EXTENDED TO |
| | DECEMBER 31ST, 2005, HOWEVER ANY AND ALL DOCUMENTS |
| | AFTER THAT DATE MUST CONTAIN THE NEW SEALS WITH THE |
| | WORDING OF *LICENSE* INSTEAD OF *CERTIFICATE*. PLEASE |
| | KNOW THAT THIS REVIEW HAS SEEN UP DATED NEW SEALS FROM |
| | THIS DESIGNER AND PERHAPS AN OLDER SEAL WAS USED |
| | INSTEAD. |
| | PLEASE KNOW THAT ANY OLD SEALS PERHAPS SHOULD BE |
| | DISCARDED SO THIS WOULD NOT CREATE INADVERTENT USE. |
| | |
| | FS 471.025. |
| | |
| | 5) NOTE: PLEASE SEE SHEETS DO NOT CONTAIN THE REQUIRED |
| | TITLE BLOCKS FOR THE ENGINEER OR FIRM OF RECORD AS |
| | REQUIRED PER FAC 61G15-23.002, FS 471.023. |
| | PLEASE INCLUDE AND COMPLETE. |
| | THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT COMMENT |
| | IS MADE BY OTHER REVIEWER(S). |
| | |
| | 6) NOTE: PLEASE SEE FBC 2004 CHAPTER 13, PREVIOUS |
| | REVIEWS MENTIONS HOW COMPLIANCE IS MET AND RESPONSE |
| | MENTIONS TO SEE REVISED PLANS, HOWEVER PLANS DID NOT |
| | SEEM TO CONTAIN INFORMATION AS NEED. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | 13-415.1.AB.1, 13-415.2 ETC?? |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | 8) NOTE: PLEASE SEE THE RECORDED NOTICE OF COMMENCEMENT |
| | SUBMITTED IS NO LONGER VALID PER FS 713.13(2). |
| | A NEW RECORDED NOC WILL BE REQUIRED BEFORE PICKING UP |
| | PERMIT. |
| | IF WORK NOTHAS NOT COMMENCED WITHIN 90DAYS OF |
| | RECORDING, SUCH NOC SHALL BECOME VOID. |
| | *MAY RE-RECORD* |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |