| Date |
Text |
| 2006-12-09 17:53:46 | * UNSAT 2ND REVIEW** |
| | |
| | ** PLEASE SEE SOME ITEMS FORM PREVIOUS REVIEW WHICH |
| | STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH AN "OK" OR "NO" DENOTING IF |
| | COMMENT WAS ADDRESSED AND ANY FURTHER EXPLANATION FOR |
| | PREVIOUS COMMENT. PLEASE ANY NOTED AS "OK/NO" MEANS |
| | PART OF A COMMENT MAY HAVE BEEN ADDRESSED BUT NOT ALL. |
| | |
| | 1) NOTE: NO, PLEASE SEE MULTIPLE ITEMS SHOWN ON PANEL |
| | SCHEDULE WHICH IS NOT LOCATED ON PLANS. PLEASE SHOW |
| | ALL. SOME ITEMS FOR CODE COMPLIANCE VERIFICATION FOR |
| | LOCATION ON PLANS COULD NOT BE VERIFIED AT THIS TIME. |
| | ** NOTE, PLEASE KNOW THAT THE LENNY'S SUB SHOP TO DATE |
| | HAS STILL NOT YET "APPLIED" FOR PERMIT. THE PLANS WERE |
| | ONLY SUBMITTED FOR "PLAN REVIEW" ONLY. THEIR PLANS WILL |
| | FALL UNDER NEW REVISIONS TO THE 2004 FBC AND THE 2005 |
| | NEC WHICH WERE ADOPTED AS OF DEC 8TH, 2006. |
| | PLEASE KNOW COMMENTS ON SOME ITEMS MAY BE DIFFERENT |
| | EVEN IF NEXT TO EACH OTHER. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE ON PLANS THE NEW CIRCUITING FOR |
| | ELECTRICAL BEING SHOWN TO EXISTING PANELS. |
| | PLEASE SUBMIT A PANEL SCHEDULE INDICATING NEW CIRCUITS |
| | AND EXISTING AS THIS ONE LARGER SPACE IS BEING DIVIDED |
| | INTO TWO SPACES AND NEED TO VERIFY THAT ALL CIRCUITING |
| | FROM THE EXISTING ONE SPACE IS NOW BEING SEPARATED. |
| | NEED TO SHOW OR EXISTING AND NEW. NEED TO VERIFY ALL |
| | CIRCUITING. 240.24,110.26, 408.4, 310.16, 240.4 |
| | ** NOTES ON PLANS MENTIONS OTHER ADJACENT SPACE UNDER |
| | REVIEW FOR SEPARATE |
| | PERMIT, HOWEVER TO THE DATE OF THIS REVIEW NO OTHER |
| | PERMIT HAS BEEN APPLIED FOR OR PLAN REVIEW FOR SAID |
| | SEPARATION OR SPACE. |
| | |
| | 2) NOTE: OK,/NO, PLEASE SEE CIRCUITING NOTE ABOVE. TO |
| | BE COMPLETED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE NEW OR EXISTING EXIT /EM LTS, SINCE |
| | THIS IS A NEW SPACE, WHERE ARE THESE LOCATED. PLEASE |
| | ALSO SEE FIRE MARSHAL'S OFFICE REVIEW NOTES. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF THESE LTS. |
| | |
| | 3) NOTE: NO. PLEASE SEE THIS SPACE EVEN THOUGH IT IS |
| | LESS THAN 5K SQ FT IS LOCATED IN A "BUILDING" LARGER |
| | THEN 5K SQ FT. PLEASE SEE DEFINITIONS OF "BUILDING" AS |
| | STATED IN THE FBC. AS THIS SPACE DOES NOT CONTAIN THE |
| | RATED "FIREWALL" IN ORDER TO CONSIDER THIS SPACE A |
| | SEPARATE BUILDING, IT DOES FALL UNDER THE REQUIREMENTS |
| | FOR LIGHTING CONTROLS. PLEASE SEE SECTIONS AS NOTED |
| | BELOW WHICH EVEN MENTION "METERED" SPACES IN A |
| | BUILDING. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 2004 CHAPTER 13 AS THIS IS A NEW |
| | BUILD-OUT AND ALL IS NOT EXISTING, THEN PLEASE SEE |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1 |
| | |
| | 4) NOTE: OK. |
| | **NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTES AT THE END OF THE |
| | REVIEW NOTESWHICH REQUESTED FOR ALL OLD/VOIDED SHEETS |
| | TO BE REMOVED FROM SETS AND FOR NEW SHEETS TO BE |
| | INSERTED IN PLACE OF OLD/VOIDED SHEETS. PLEASE MAKE TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. PLEASE DO NOT |
| | SUBMIT LOOSE SHEETS NOT IN SETS. THIS WILL HELP IN THE |
| | REVIEW AND PROCESSING OF PLANS. |
| | CONTRACTOR WILL BE CALLED IN TO DO THIS IF PLANS ARE |
| | NOT PLACED INTO SETS WHEN RESUBMITTING FOR THE NEXT |
| | REVIEW. |
| | |
| | ** PLEASE KNOW, THERE IS SOME |
| | INFORMATION WHICH IS NOT CLEAR AT THIS |
| | TIME AND NEEDS TO BE VERIFIED. PLEASE |
| | SEE ANY POSSIBLE NOTES FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-12-09 17:26:28 | PLANS REMOVED FROM INCOMING AND WILL BE ROUTED BACK TO |
| | INCOMING ONCE REVIEW IS DONE. |