| 2006-09-29 00:00:00 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE INDICATE ON PLANS THE |
| | NEW CIRCUITING FOR ELECTRICAL BEING |
| | SHOWN TO EXISTING PANELS. |
| | PLEASE SUBMIT A PANEL SCHEDULE |
| | INDICATING NE CIRCUITS AND EXISTING AS |
| | THIS ONE LARGER SPACE IS BEING DIVIDED |
| | INTO TWO SPACES AND NEED TO VERIFY THAT |
| | ALL CIRCUITING FROM THE EXISTING ONE |
| | SPACE IS NOW BEING SEPARATED. |
| | NEED TO SHOW OR EXISTIGN AND NEW. NEED |
| | TO VERIFY ALL CIRCUITING . 240.24,110.26,408.4,310.16, |
| | 240.4 |
| | |
| | |
| | ** NOTES ON PLANS MENTIONS OTHER |
| | ADJACENT SPACE UNDER REVIEW FOR SEPARATE |
| | PERMIT, HOWEVER TO THE DATE OF THIS |
| | REVIEW NO OTHER PERMIT HAS BEEN APPLIED |
| | FOR OR PLAN REVIEW FOR SAID SEPARATION |
| | OR SPACE. |
| | |
| | 2) NOTE: PLEASE INDICATE NEW OR EXISTING |
| | EXIT /EM LTS, SINCE THIS IS A NEW SPACE, |
| | WHERE ARE THESE LOCATED. PLEASE ALSO SEE |
| | FIRE MARSHAL'S OFFICE REVIEW NOTES. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | THESE LTS. |
| | |
| | 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13 |
| | AS OF THIS IF THIS IS NEW BUILD -OUT AND |
| | ALL IS NOT EXISTING, THEN PLEASE SEE 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3, |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1 |
| | |
| | 4) NOTE: PLEASE SEE THE FOLLOWING CODES |
| | SHALL BE STATED ON THE PLANS AT A MIN. |
| | PLEASE SEE 2002 NFPA-70(NEC), 2003 |
| | NFPA-101 (SHOWS 2000), 2002 NFPA-72 |
| | |
| | ** PLEASE KNOW, THERE IS SOME |
| | INFORMATION WHICH IS NOT CLEAR AT THIS |
| | TIME AND NEEDS TO BE VERIFIED. PLEASE |
| | SEE ANY POSSIBLE NOTES FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |