Plan Review Notes For Permit 06090881
Permit Number 06090881
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-13 07:04:21 
  
 DENIED
  
 1) PER 1609.6.1 FBC THE SIMPLIFIED CALCULATION METHOD
 FOR WIND LOADS SHALL NOT BE USED TO DETERMINE WIND
 PRESSURES FOR BUILDINGS OVER 60 FT IN HEIGHT. PLEASE
 SUBMIT ENGINEERED CALCULATIONS
  
 2) REMODEL PERMITS THAT ARE FOR THE REPLACEMENT OF
 EXISTING DOORS OR WINDOWS SHALL INCLUDE A PLAN VIEW
 LAYOUT SHOWING THE LOCATION OF ALL OPENINGS AND THE
 SIZES AND LOCATION OF DOOR AND WINDOWS THAT WILL BE
 REPLACED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716