| Date |
Text |
| 2006-10-05 00:00:00 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE ENGINEER OF RECORD SHALL INDICATE |
| | INFORMATION REQUIRED BY 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE. ALSO SEAL |
| | ALL SHEETS. |
| | |
| | 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC |
| | AND 106.3.5.4(8) FBC. |
| | |
| | 3} PROVIDE A LOAD CALCULATION PER |
| | 220.31, INCLUDE ADDED LOADS. |
| | |
| | 4} INDICATE THE RATING OF EXISTING |
| | SERVICE . 215.5 NEC. |
| | |
| | 5} SMOKE DETECTORS MUST BE INSTALLED TO |
| | COMPLY WITH R313.1 RESIDENTIAL FLORIDA |
| | BUILDING CODE. |
| | |
| | 6} BATH CIRCUIT REQUIRED TO HAVE A 20 |
| | AMP RECEPTACLE PER 210.11(C)(3), LOCATED |
| | PER 210.52(D), AND BE GFI PROTECTED PER |
| | 210.8(A)(1). INDICATE SAME ON PLAN. |
| | |
| | 7} 210.52(E) OUTDOOR OUTLETS. FOR A |
| | ONE-FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE AT GRADE LEVEL AND NOT MORE |
| | THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL |
| | BE INSTALLED AT THE FRONT AND BACK OF |
| | THE DWELLING. SEE 210.8(A)(3). |
| | |
| | PLEASE NOTE AN ELECTRICAL PERMIT IS |
| | REQUIRED FOR THE SCOPE OF WORK PURPOSED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |