Plan Review Notes
Plan Review Notes For Permit 06090858
Permit Number 06090858
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-05 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE
 INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE. ALSO SEAL
 ALL SHEETS.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC.
  
 3} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS.
  
 4} INDICATE THE RATING OF EXISTING
 SERVICE . 215.5 NEC.
  
 5} SMOKE DETECTORS MUST BE INSTALLED TO
 COMPLY WITH R313.1 RESIDENTIAL FLORIDA
 BUILDING CODE.
  
 6} BATH CIRCUIT REQUIRED TO HAVE A 20
 AMP RECEPTACLE PER 210.11(C)(3), LOCATED
 PER 210.52(D), AND BE GFI PROTECTED PER
 210.8(A)(1). INDICATE SAME ON PLAN.
  
 7} 210.52(E) OUTDOOR OUTLETS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE
 THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. SEE 210.8(A)(3).
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS
 REQUIRED FOR THE SCOPE OF WORK PURPOSED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW