2006-10-17 18:01:29BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2-AFTER ALL DRAWINGS ARE REVISED, PAY PALM BEACH
 COUNTY IMPACT FEES. BRING BACK STAMPED DRAWINGS AND
 COPY OF THE PAID RECEIPT.
  
 3-A)ENGINEER NEEDS TO PROVIDE ALL HIS INFORMATION
 IN ALL DRAWINGS AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
 B)ENGINEER NEEDS TO SIGN AND SEAL ALL DRAWINGS.
  
  
 4-WHY ARE BOTH DRAWINGS LABELED A-101. REVISE AS
 REQUIRED.
  
 5-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER
 13 FBC 2004.
  
 6-ENGINEER TO SPECIFY HOW MUCH AREA IS ADDED TO THE
 HOUSE TO DETERMINE PERMIT VALUATION AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.
  
 7-ENGINEER TO SPECIFY SPECIFIC BUILDING CODE AND ALL
 THE DESIGN CRITERIA AS REQUIRED BY SEC. R301 2004
 FLORIDA RESIDENTIAL CODE.
  
 8-ENGINEER TO PROVIDE COMPLETE ENGINEERING ANALYSIS
 SHOWING HOW CAN THE 2"X10" FLOOR JOISTS EXPAND UP TO
 24'-0".SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- DRAWINGS TO PROVIDE COMPLETE SPECS SHOWING
 COMPLIANCE WITH WOOD PROTECTION AGAINST DECAY. SEE SEC.
 R319 2004 FLORIDA RESIDENTIAL CODE.
  
 10-PROVIDE COMPLETE EXTERIOR ELEVATIONS. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 11-CLARIFY IF HOME IS GOING TO HAVE MECHANICAL
 VENTILATION. OTHERWISE, PROVIDE VENTILATION AS REQUIRED
 BY SEC. R303.1 2004 FLORIDA RESIDENTIAL CODE.
  
 12-SPECIFY WINDOW TYPES AND SIZES TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS SEC. R310 2004
 FLORIDA RESIDENTIAL CODE.
  
 13-SPECIFY SAFETY GLASS FOR BATHROOM WINDOW. SEC.
 R308.4 2004 FLORIDA RESIDENTIAL CODE.
  
 14-PROVIDE COMPLETE SPECIFICATIONS FOR FOOTINGS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15-PROVIDE COMPLETE SPECIFICATIONS FOR ATTACHMENT OF
 NEW FOOTING TO EXISTING. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004
  
 16-PROVIDE COMPLETE DRAWINGS AND SPECIFICATIONS FOR
 CRAWL SPACE TO COMPLY WITH SEC. R408 2004 FLORIDA
 RESIDENTIAL CODE.
  
 17-SECTION A-A:
 A)PROVIDE COMPLETE SPECIFICATIONS. SPECIFY ALL
 CONNECTORS, ROOF VENTILATION, STUCCO THICKNESS, WALL
 SHEATHING FASTENING, CONNECTION OF WALL TO FOUNDATION
 AND ROOF,THICNESS OF VAPOR BARRIER, TERMITE
 PROTECTION,DIMENSIONS FOR FOOTING EMBEDMENT INTO
 GRADE,CONSTRUCTION MATERIALS UNDERSIDE OF FLOOR
 FRAMING, ETC. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B)R19 INSULATION DOESN'T FIT IN 2X4 STUDS. REVISE
 AS REQUIRED.
 C) CLARIFY WHY 2" INSULATION ON FOUNDATION AND
 PROVIDE COMPLETE SPECS AND LOCATION FOR SUCH
 INSULATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 D) REVISE ROOF FRAMING DETAIL TO MATCH ACTUAL ROOF
 FRAMING PLAN.
  
 18-SPECIFY ATTIC ACCESS. SEC. R3807 2004 FLORIDA
 RESIDENTIAL CODE.
  
 19-NEED STEPS BY REAR DOOR.SEE SECTIONS R311.5.3
 AND R312 2004 FLORIDA RESIDENTIAL CODE.
  
 20-MIN. HALLWAY DIMENSION IS 3'-0".CLEARANCEIN
 HALLWAY BY WASH AREAIS REDUCED BY PUTTING WASHER AND
 DRYER. REVISE AS REQUIRED. SEC. R311.3 2004 FLORIDA
 RESIDENTIAL CODE.
  
 21-SPECIFY ROOF VENTILATION. SEC. R806 2004 FLORIDA
 RESIDENTIAL CODE.
  
 22-IF INTERIOR WALL CONSTRUCTION IS 2X4'S, THEN WHY
 PROVIDING DETAIL FOR METAL PARTITION.
  
 23-DEPTH OF CLOSETS IN NEW BEDROOMS ARE TOO NARROW.
 CLOTHES DON'T FIT. REVISE AS REQUIRED.
  
 24- PROVIDE DIMENSIONS ON PLOT PLAN.
  
 25- PROVIDE SOIL TEST REPORT.
  
 26-ROOF FRAMING PLAN IS WRONG. PROVIDE COMPLETE ROOF
 FRAMING PLAN INCLUDING ATTACHMENT OF NEW ROOF TO
 EXISTING ROOF. CLARIFY IF USING PREFABRICATED ROOF
 TRUSSES OR CONVENTIONAL FRAMING. PROVIDE COMPLETE SPECS
 FOR EITHER ONE. PROVIDE UPLIFT LOADS AND TRUSS
 CONNECTOR SCHEDULE. SECTION 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 27-SPECIFY NAILING SIZE AND SPACING FOR ROOF
 SHEATHING. SEE TABLE 2304.9.1 2004 FBC 2004.
  
 28-PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) ALL USP OR SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED BY THE ENGINEER ON PLANS AND DETAILS.
  
 29-ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITTING ALL PRODUCT APPROVALS. SEC. 106.3 CITY
 AMENDMENTS TO FBC 2004.
  
 30- STORM SHUTTERS:
 A) PROVIDE CLEAR AND LEGIBLE DRAWINGS.
 B) PROVIDE KEY PLAN AND COMPLETE INSTALLATION
 SCHEDULE.SEE ATTACHED SAMPLE OF INSTALLATION
 SCHEDULE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712