2006-09-29 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $8,222.ADDITIONAL PERMIT FEES ARE DUE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 WINDOWS, IMPACT PROTECTION, ROOFING AND
 HARDIE PLANK SIDING AND STRAPS AND
 TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT A ROOF SHEATHING NAILING
 SCHEDULE.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.SHOW SPACING FOR FASTENERS ON
 LEDGER DETAIL.
  
 11.SHOW CEILING HEIGHT COMPLYING WITH
 R-305.
  
 12.DESIGN PARAMETERS SHOULD BE
 DESIGNED TO ASCE-7-02.
  
 13.SHOW EXISTING WINDOWS IN BEDROOM
 INCLUDING SIZES AND TYPE AND SILL HEIGHT
 SO THAT EMERGENCY ESCAPE AND RESCUE
 OPENING SIZES CAN BE VARIFIED R-310.
  
 14.PROTECTION AGAINS DECAY R 319
 1.WOOD JOISTS OR THE BOTTOM OF A
 WOOD STRUCTURAL FLOOR WHEN CLOSER THAN
 18 INCHES OR WOOD GIRDERS WHEN CLOSER
 THAN 12 INCHES TO THE EXPOSED GROUND IN
 CRAWL SPACES OR UNEXCAVATED AREA LOCATED
 WITHIN THE PERIPHERY OF THE BUILDING
 FOUNDATION.
 2.ALL WOOD FRAMING MEMBERS THAT
 REST ON CONCRETE OR MASONRY EXTERIOR
 FOUNDATION WALLS AND ARE LESS THAN 8
 INCHES FROM THE EXPOSED GROUND.
 5.WOOD SIDING, SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING
 HAVING A CLEARANCE OF LESS THAN 6 INCHES
 FROM THE GROUND.
  
 NOTE;FOOTING THICKNESS OF 6" AND
 FOOTING DEPTH OF 12" BELOW GRADE ARE
 BOTH AT THE MINIMUM REQUIRED BY CODE.
 JUST A NOTE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  