| Plan Review Notes For Permit 06090792 |
| Permit Number |
06090792 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-05 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | 2- FLORIDA PRODUCT APPROVAL COVER PAGE | | | FL1850-R1 CALLS FOR ACCORDION SHUTTERS | | | DRAWING NO 05-195. DRAWINGS SUBMITTED | | | ARE NO 05-196. NEED TO PROVIDE DRAWINGS | | | THAT MATCH FLORIDA COVER PAGE. | | | | | | 3- A) ANCHOR TYPE SPECIFIED ON | | | INSTALLATION SCHEDULE TO MATCH ANCHOR | | | SPECIFIED ON THE DRAWINGS. SEE PAGE 11 | | | OF 14 OF ACCORDION SHUTTERS DRAWINGS AND | | | REVISE AS REQUIRED. | | | | | | B) 2 1/2" EDGE DISTANCE REQUIRES ANCHOR | | | SPACING TO BE REDUCED BY MULTIPLIER | | | SHOWN ON TABLE IN DRAWING #11. REVISE AS | | | REQUIRED. | | | | | | 4- WIND LOAD SCHEDULE CHART IS NOT | | | REQUIRED FOR BUILDINGS WITH MEAN ROOF | | | HEIGHT LESS THAN 30'-0". CONTRACTOR CAN | | | USE TABLE 1609.6B OF FBC 2004 TO | | | CALCULATE THE DESIGN PRESSURES. ON THE | | | OTHER HAND, IF SUCH SCHEDULE IS | | | SUBMITTED, THEN 2 COPIES WITH ORIGINAL | | | SEAL, SIGNATURE AND DATE ARE REQUIRED | | | PER CHAPTER 471 FLORIDA STATUTES. ONLY | | | ONE ORIGINAL SUBMITTED AT THIS TIME. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|