2006-10-05 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- FLORIDA PRODUCT APPROVAL COVER PAGE
 FL1850-R1 CALLS FOR ACCORDION SHUTTERS
 DRAWING NO 05-195. DRAWINGS SUBMITTED
 ARE NO 05-196. NEED TO PROVIDE DRAWINGS
 THAT MATCH FLORIDA COVER PAGE.
  
 3- A) ANCHOR TYPE SPECIFIED ON
 INSTALLATION SCHEDULE TO MATCH ANCHOR
 SPECIFIED ON THE DRAWINGS. SEE PAGE 11
 OF 14 OF ACCORDION SHUTTERS DRAWINGS AND
 REVISE AS REQUIRED.
  
 B) 2 1/2" EDGE DISTANCE REQUIRES ANCHOR
 SPACING TO BE REDUCED BY MULTIPLIER
 SHOWN ON TABLE IN DRAWING #11. REVISE AS
 REQUIRED.
  
 4- WIND LOAD SCHEDULE CHART IS NOT
 REQUIRED FOR BUILDINGS WITH MEAN ROOF
 HEIGHT LESS THAN 30'-0". CONTRACTOR CAN
 USE TABLE 1609.6B OF FBC 2004 TO
 CALCULATE THE DESIGN PRESSURES. ON THE
 OTHER HAND, IF SUCH SCHEDULE IS
 SUBMITTED, THEN 2 COPIES WITH ORIGINAL
 SEAL, SIGNATURE AND DATE ARE REQUIRED
 PER CHAPTER 471 FLORIDA STATUTES. ONLY
 ONE ORIGINAL SUBMITTED AT THIS TIME.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712