| Notes |
| Date |
Text |
| 2006-10-17 15:07:08 | BUILDING REVIEW 2ND CHECKLIST: | | | 1- ANCHOR TYPE SPECIFIEDIN THE INSTALLATION SCHEDULE | | | DOESN'T MATCH ANCHOR SPECIFIED ON ACCORDION SHUTTERS | | | AND STORM PANELS DRAWINGS. REVISE AS REQUIRED. | | | | | | 2- REVISE ANCHOR SPACING ACCORDING TO THE EDGE | | | DISTANCE. SEE TABLES IN ACCORDION SHUTTERS AND STORM | | | PANELS DRAWINGS AND REVISE AS REQUIRED. | | | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|