2006-11-08 18:34:29BUILDING PLAN REVIEW
 PERMIT: 06090766
 ADD: 615 MONROE DR
 CONT:MTC REMODELING INC.
 TEL: (561)655-5956
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW2ND
 ACTION: DENIED
  
 1) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
  
 2)FBC. 1609.1.4STRUCTURAL MEMBERS AND SYSTEMS AND
 COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.HOW WILL THE
 PRECAST CONCRETE BE ANCHORED IN THE GROUND?IF THE
 PRECAST CONCRETE WILL BE PLACE ON GRADE PROVIDE THE
 ENGINEERING DRAWINGS WHIC STATE THAT THIS DESIGW WILL
 MEET THE 140MPH 3SEC WIND GUST.
  
 3)ONCEAGAIN THE DRAWINGS SUBMITTED ARE NOT CLEAR.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVENT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. FBC. 106.1.1
  
 4)SHOW THE FRONT/ LEFT AND RIGHT ELEVATIONS OF THE
 PROJECT. THE DRAWINGS PROVIDEDARE NOT DRAWN TO THE
 SCALE SPECIFIED. THE DETAIL DRAWINGS ON THE SHEET ARE
 INSUFFICIENT. INDICATE THE LOAD OF THE DECK ACCORDING
 TO TABLE 1607.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  