Plan Review Notes For Permit 06090712
Permit Number 06090712
Review Stop B
Sequence Number 3
Notes
Date Text
2006-12-01 09:08:05DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE 2004 FBC EXISTING BUILDING CODE UNDER
 APPLICABLE CODES ON G-002.
  
 3) ALSO ON G-002 SPECIFY THE LEVEL OF ALTERATION AS
 DESIGNATED IN CHAPTER 3 OF THE FBC EXISTING BUILDING
 CODE. THIS PROJECT IS A LEVEL 2 ALTERATION.
  
 4)FBC 11-4.24.3 REQUIRES KNEE CLEARANCE UNDERNEATH
 SINKS. DETAIL D ON A-104 HAS A CABINET WITH SHELF SHOWN
 BELOW THE SINK.
  
 5) THE DETAILS ON A-104 ARE INCORRECTLY LABELED AS
 A-103.
  
 6) THE REDLINE CORRECTIONS TO DRAWING MW-3 ON A-104 ARE
 REQUIRED TO BE INITIALED AND DATED BY THE DESIGNER OF
 RECORD THAT HAS SIGNED AND SEALED THE DRAWING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  