2006-11-09 10:00:30DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ************PLAN REVIEW ONLY************
 SECOND REVIEW
  
 1. SHT A-104 DETAIL MW-3. THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW
 COMPLIANCE WITH SECTION 11-4.24.
 A. OK
 B. 11-4.24.3 KNEE CLEARANCE - NOT SHOWN
 C. OK
 D. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH IS REQUIRED, MAXIMUM
 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED IN CLEAR FLOOR SPACE. - NOT SHOWN
 UNDERNEATH THE SINK AS REQUIRED.
 E. OK
 F. 11-4.24.7 FAUCETS. - NOT ADDRESSED
  
 2. OK
 3. OK
  
 **************NEW COMMENT**************
  
 1B. SEE COMMENT #2 FROM ELECTRICAL REVIEW WITH RESPECT
 TO THE TITLE BLOCK INFORMATION REQUIRED FOR THE ADDRESS
 AND SUITE NUMBER FOR PROJECT. FAC 61G1-16.004(1) & FS
 481.2055.
  
 REVIEW BY KEN STEVENS