| 2006-10-23 09:33:57 | **FOR PLAN REVIEW ONLY NOT FOR PERMIT** | | | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 9-28-06 NOTE #2. | | | SEE PAGE ME-103 CONDENSER UNIT | | | MOUNTING DETAIL, PLEASE SHOW HOW | | | CONDENSER STAND NEEDS TO BE SECURED TO | | | ROOF, AND HOW CONDENSER UNIT NEEDS TO BE | | | SECURED TO STAND TO WITHSTAND 140 MPH | | | WINDS, PER 2004 FBC 1609. | | | (THE CITY OF WPB DOES NOT PERMIT CABLE STRIPS OVER | | | CONDENSRE UNITS), SHOW SIZES OF ANCHOR BOLT FROM | | | CONDENSER UNIT TO STAND. | | | SEE PIPE SUPPORT DETAIL NEED TO SHOW HOW THE STEEL | | | PLATE FROM THE CONDENSER STAND IS TO BE SECURED TO THE | | | STEEL JOIST. | | | | | | 2) PLANS PAGE ME-001 THROUGH ME-104 NEED TO BE SEALED | | | BY THE ENGINEER, PER FAC 61G15-23.002. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|