Plan Review Notes
Plan Review Notes For Permit 06090712
Permit Number 06090712
Review Stop M
Sequence Number 2
Notes
Date Text
2006-10-23 09:33:57**FOR PLAN REVIEW ONLY NOT FOR PERMIT**
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 9-28-06 NOTE #2.
 SEE PAGE ME-103 CONDENSER UNIT
 MOUNTING DETAIL, PLEASE SHOW HOW
 CONDENSER STAND NEEDS TO BE SECURED TO
 ROOF, AND HOW CONDENSER UNIT NEEDS TO BE
 SECURED TO STAND TO WITHSTAND 140 MPH
 WINDS, PER 2004 FBC 1609.
 (THE CITY OF WPB DOES NOT PERMIT CABLE STRIPS OVER
 CONDENSRE UNITS), SHOW SIZES OF ANCHOR BOLT FROM
 CONDENSER UNIT TO STAND.
 SEE PIPE SUPPORT DETAIL NEED TO SHOW HOW THE STEEL
 PLATE FROM THE CONDENSER STAND IS TO BE SECURED TO THE
 STEEL JOIST.
  
 2) PLANS PAGE ME-001 THROUGH ME-104 NEED TO BE SEALED
 BY THE ENGINEER, PER FAC 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.