Plan Review Notes
Plan Review Notes For Permit 06090712
Permit Number 06090712
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-22 16:47:02***** UNSAT 2ND REVIEW******
  
 *** PLEASE KNOW, THIS PROJECTIS STILLONLY
 BEEN SUBMITTED FOR "PLAN REVIEW" ONLY
 AND HAS NOT BEEN SUBMITTED FOR PERMIT.
 PLEASE SEE SOME NOTE SFROM PREVIOUS REVIEW AND SOME NEW
 NOTES DUE TO THE PLANS SUBMITTED. PLEASE SEE NOTES
 BELOW ARE TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH NEW
 NOTES ADDED TO BOTTOM.
  
 1) NOTE: OK.
  
 2) NOTE:NO/OK. PLEASE SEE PLANS ARE NOW BEING
 SUBMITTED WITH A SUITE NUMBER OF #275?? PLEASE SEE
 ORIGINAL "PLAN REVIEW" APPLICATION SHEET INDICATED
 #210. PLEASE SEE AN EXTENSION WAS GRANTED AND ISSUED BY
 THE ADDRESSING REVIEWER FOR SUITE #210, HOWEVER NOW
 SHOWS #275. PLEASE CORRELATE THIS WITH THE ADDRESSING
 REVIEWER AND PLACE ON FINAL TITLE BLOCKS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ALL TITLE BLOCKS
 SHALL CONTAIN THE RELEVANT ADDRESS AND
 SUITE NUMBER FOR LOCATION OF PROJECT.
 FAC 61G1-16.004, FAC 61G15-23.002
 REQUIRED FOR ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS
 ADDRESSED BY OTHER TRADES.
  
 3) NOTE: NO, SAME NOTE.
 PLEASE SEE NO SCHEDULING WAS SUBMITTED.
 PLEASE SEE TIMES ONE OVER RIDES ARE NOT INDICATED ON
 SYMBOL LEGAND ON DEVICES.
 PLEASE SEE A SYSTEM IS NOT SHOWN.
 PLEASE SEE NO PERFORMANCE CALCULAITONS WERE SUBMITTED.
 ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER 13.
 PLEASE SUBMIT AND SHOW THE SYSTEM WHICH
 IS REQUIRED FOR LIGHTING CONTROLS.
 PLEASE SUBMIT COMPLETE SCHEDULING.
 PLEASE SUBMIT AND SHOW ALL LOCATIONS OF
 OVER-RIDE DEVICES. PLEASE SEE CODE WITH
 RESPECT TO LOCATIONS AS THE OCCUPANT
 MUST BE ABLE TO SEE THE LIGHTING WHICH
 IS BEING CONTROLLED.
 PLEASE INDICATE THE DEVICES AND THE
 TIMES PERMITTED FOR OVER-RIDES (MAX
 TIMES).
 PLEASE SUBMIT PERFORMANCE CALCULATIONS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 AND
 TABLES. 415.
  
 4) NOTE: NO, PLEASE SEE ALL LOADS ON THE EXSITNG
 WIREWAY NEED TO BE REFLECTED INCLUDING NEW LOADS PER
 NEC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE LOADS ON EXISING
 WIRE-WAY WHICH NEW SERVICE FOR TENANT IS
 BEING TAPPED, ALONG WITH EXISTING FEED
 FROM MDP.
 220, 220.3,220.10,220.11,220.13, ETC
 215.3 AND 230.42 ETC FOR CONTINOUS
 LOADS.
  
 5) NOTE:OK.
  
 6) NOTE:NO, ONLY REFERENCE TO THE NEC ARTICLES WHICH
 WERE GIVEN ON PREVIOUS REVIEW FOR COMPLIANCE WAS PLACED
 ON PLANS.PLEASE KNOW, PLACING NOTES ON PLANS IN LEIU
 OF REQUIRED DETAIL(S) IS NOT ACCEPTABLE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE A NOTE FOR A
 "FLOATING NEUTRAL" IN TENANT METERCAN. 250.6.250.24
  
 7) NOTE: OK.
  
 8) NOTE: OK. HOWEVER PLEASE SEE DESIGNATION FOR ROOM IS
 NOT ON ELECTRICLA POWER PLAN.
  
  
 9) NOTE: NO, PLEASE INDICATE FOR ALL NEW.
 110.9, 240.12
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL AIC RATINGS
 FOR ALL SERVICE EQUIPMENT.
 110.9.
  
 10) NOTE: NO, PLEASE INDICATE AND SHOW ATTACHMENT
 LOCATION. QUOTING OF CODE IN LEIU OF SPECIFIC
 INFORMATION IS NOT PERMITED.
 AN ASSUMPTION OF THE CONTRACTORS WORK CAN NOT BE
 EXPECTED.
  
 ** PREVIOUS REVIEW NOTE **
 ' PLEASE INDICATE AND SHOW THE
 LOCATION OF THE GROUND ATTACHMENT FOR
 THE THE TRANSFORMER. PLEASE SEE 250.30,
 250.66, 250.20 ETC.
  
 ** NEW NOTES**
  
 11) NOTE: PLEASE SEE NEW ME PLANS ARE NOT SEALED BY THE
 DESIGNER OF RECORD AS REQUIRED UNDER FS 471.025, AND
 FAC 61G15-23.002.
 PLEASE SEE BOTH SETS ARE THE SAME. AN EMBOSSED RAISED
 SEAL IS REQUIRED.
  
 12) NOTE: PLEASE CLARIFY WHAT IS SHOWN AS "H2C AND
 "L2C" ON RISER. ARE THESE PART OF THE SAME TENANT
 SPACE? IF SO, MAINS ARE NOT GROUPED PER 230.72, ETC.
 PLEASE KNOW, THIS CAN BE REMOVED IF NOT PART OF THIS
 TENANT.
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT BEEN
 PROVIDED, THERE MAY BE FUTURE COMMENTS.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICHMAY AFFECT PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]