Plan Review Notes
Plan Review Notes For Permit 06090712
Permit Number 06090712
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-27 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
  
 ************PLAN REVIEW ONLY************
  
 1. SHT A-104 DETAIL MW-3. THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW
 COMPLIANCE WITH SECTION 11-4.24.
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH IS REQUIRED, MAXIMUM
 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED IN CLEAR FLOOR SPACE.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS.
  
 2. SHT ME-2 CONDENSATE NOT APPROVED TO
 DRAIN INTO THE SANITARY SYSTEM. CITY
 CODE 90-125(B)(5). CONDENSATE SHALL
 DRAIN SEPARATELY OUT OF THE BUILDING AND
 CONNECT TO STORM, (WITH A RELIEF VENT OR
 GOOSENECK AS IT EXITS THE BUILDING), A
 CATCH BASIN, A DRYWELL, OR INTO A
 PLANTED AREA TERMINATING 6" ABOVE THE
 GROUND LEVEL.
  
 3. SHT ME-2 WATER RISER DIAGRAM
 ISOMETRIC. THE WATER HAMMER ARRESTOR
 PROVIDED SHALL BE LOCATED NEAR THE
 FIXTURE, IN AN "EFFECTIVE RANGE", NOT IN
 THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]