| Plan Review Notes For Permit 06090712 |
| Permit Number |
06090712 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-27 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 11 | | | MUNICIPAL CODE | | | | | | ************PLAN REVIEW ONLY************ | | | | | | 1. SHT A-104 DETAIL MW-3. THE FOLLOWING INFORMATION IS | | | REQUIRED TO SHOW | | | COMPLIANCE WITH SECTION 11-4.24. | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH | | | D. 11-4.24.5 CLEAR FLOOR SPACE - | | | FORWARD APPROACH IS REQUIRED, MAXIMUM | | | 19" UNDERNEATH THE SINK. CABINET DOORS | | | ARE NOT APPROVED IN CLEAR FLOOR SPACE. | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES | | | F. 11-4.24.7 FAUCETS. | | | | | | 2. SHT ME-2 CONDENSATE NOT APPROVED TO | | | DRAIN INTO THE SANITARY SYSTEM. CITY | | | CODE 90-125(B)(5). CONDENSATE SHALL | | | DRAIN SEPARATELY OUT OF THE BUILDING AND | | | CONNECT TO STORM, (WITH A RELIEF VENT OR | | | GOOSENECK AS IT EXITS THE BUILDING), A | | | CATCH BASIN, A DRYWELL, OR INTO A | | | PLANTED AREA TERMINATING 6" ABOVE THE | | | GROUND LEVEL. | | | | | | 3. SHT ME-2 WATER RISER DIAGRAM | | | ISOMETRIC. THE WATER HAMMER ARRESTOR | | | PROVIDED SHALL BE LOCATED NEAR THE | | | FIXTURE, IN AN "EFFECTIVE RANGE", NOT IN | | | THE CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|