Plan Review Notes
Plan Review Notes For Permit 06090712
Permit Number 06090712
Review Stop M
Sequence Number 1
Notes
Date Text
2006-09-28 00:00:00**FOR PLAN REVIEW ONLY NOT FOR PERMIT**
 *** DENIED ***
 1) SEE PAGE ME-001, PLEASE PROVIDE
 OUTDOOR AIR CALCULATIONS, PER 2004 FBC/M
 403.2 .
  
 2) SEE PAGE ME-103 CONDENSER UNIT
 MOUNTING DETAIL, PLEASE SHOW HOW
 CONDENSER STAND NEEDS TO BE SECURED TO
 ROOF, AND HOW CONDENSER UNIT NEEDS TO BE
 SECURED TO STAND TO WITHSTAND 140 MPH
 WINDS, PER 2004 FBC 1609.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.