| Plan Review Notes For Permit 06090712 |
| Permit Number |
06090712 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-28 00:00:00 | **FOR PLAN REVIEW ONLY NOT FOR PERMIT** | | | *** DENIED *** | | | 1) SEE PAGE ME-001, PLEASE PROVIDE | | | OUTDOOR AIR CALCULATIONS, PER 2004 FBC/M | | | 403.2 . | | | | | | 2) SEE PAGE ME-103 CONDENSER UNIT | | | MOUNTING DETAIL, PLEASE SHOW HOW | | | CONDENSER STAND NEEDS TO BE SECURED TO | | | ROOF, AND HOW CONDENSER UNIT NEEDS TO BE | | | SECURED TO STAND TO WITHSTAND 140 MPH | | | WINDS, PER 2004 FBC 1609. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|