Plan Review Notes
Plan Review Notes For Permit 06090712
Permit Number 06090712
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-03 00:00:00***** UNSAT ******
  
 *** PLEASE KNOW, THIS PROJECT HAS ONLY
 BEEN SUBMITTED FOR "PLAN REVIEW" ONLY
 AND HAS NOT BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE BE SURE TO STATE THE
 FOLLOWING MINIMUM CODES RELVANT TO THE
 DESIGNS OF PROJECT SUBMITTED.
 2002 NFPA-72, 2002 NFPA-70, 2003
 NFPA-101, 2004 FBC.
  
 2) NOTE: PLEASE SEE ALL TITLE BLOCKS
 SHALL CONTAIN THE RELEVANT ADDRESS AND
 SUITE NUMBER FOR LOCATION OF PROJECT.
 FAC 61G1-16.004, FAC 61G15-23.002
 REQUIRED FOR ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS
 ADDRESSED BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13.
 PLEASE SUBMIT AND SHOW THE SYSTEM WHICH
 IS REQUIRED FOR LIGHTING CONTROLS.
 PLEASE SUBMIT COMPLETE SCHEDULING.
 PLEASE SUBMIT AND SHOW ALL LOCATIONS OF
 OVER-RIDE DEVICES. PLEASE SEE CODE WITH
 RESPECT TO LOCATIONS AS THE OCCUPANT
 MUST BE ABLE TO SEE THE LIGHTING WHICH
 IS BEING CONTROLLED.
 PLEASE INDICATE THE DEVICES AND THE
 TIMES PERMITTED FOR OVER-RIDES (MAX
 TIMES).
 PLEASE SUBMIT PERFORMANCE CALCULATIONS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 AND
 TABLES. 415.
  
 4) NOTE: PLEASE PROVIDE LOADS ON EXISING
 WIRE-WAY WHICH NEW SERVICE FOR TENANT IS
 BEING TAPPED, ALONG WITH EXISTING FEED
 FROM MDP.
 220, 220.3,220.10,220.11,220.13, ETC
 215.3 AND 230.42 ETC FOR CONTINOUS
 LOADS.
  
 5) NOTE: PLEASE SEE EXSTING FEED FROM
 THE MDP IS SHOWN #3'S ON A 200A
 BREAKER/OCP WHICH IS NOT PERMITTED.
 240.4,310.16
  
 6) NOTE: PLEASE INDICATE A NOTE FOR A
 "FLOATING NEUTRAL" IN TENANT METERCAN. 250.6.250.24
  
 7) NOTE: PLEASE SEE LOAD ON H2D EXCEEDS
 THE RATING OF THE EQUIPMENT FEEDING THIS
 PANEL. PLEASE SEE RISER ONLY SHOWS A 60A
 FEED,
 PLEASE ADJUST.
 240, 408 ETC
  
 8) NOTE: PLEASE INDICATE THE MIN
 CLEARENCES IN FRONT OF ALL ELECTRICAL
 SERVICE EQUIPMENT.
 110.26, 450.13, 450.9 ETC.
  
 9) NOTE: PLEASE INDICATE ALL AIC RATINGS
 FOR ALL SERVICE EQUIPMENT.
 110.9.
  
 10) NOTE: PLEASE INDICATE AND SHOW THE
 LOCATION OF THE GROUND ATTACHMENT FOR
 THE THE TRANSFORMER. PLEASE SEE 250.30,
 250.66, 250.20 ETC.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICHMAY AFFECT PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  