| 2006-10-02 00:00:00 | SUBMITTED FOR PLAN REVIEW NOT FOR PERMIT |
| | |
| | |
| | |
| | DENIED BY BUILDING |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SPECIFY THE LEVEL OF ALTERATION FOR |
| | THE PROJECT AS DEFINED IN THE 2004 FBC |
| | EXISTING BUILDING CODE. |
| | |
| | 3) SPECIFY THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDING USING THE 2004 FBC |
| | DESIGNATION. |
| | |
| | 4) ON SHEET G-002 BASED ON THE 2004 FBC |
| | THE BUILDING HEIGHT AND AREA TABLE IS |
| | 503 AND THE TABLE FOR FIRE WALL RATING |
| | IS 601. PLEASE CORRECT. |
| | |
| | 5) ON G-002 THE OCCUPANT LOAD FOR 6619 |
| | SQFT IS 67 PERSONS. PLEASE CORRECT. |
| | |
| | 6) ON G-002 THE EXIT CAPACITY SHOULD BE |
| | 67 X 0.2". PLEASE CORRECT. |
| | |
| | 7) FBC 1013.2 DOES NOT ALLOW EGRESS TO |
| | PASS THROUGH A KITCHEN. ROOM 113 ON |
| | A-102 APPEARS TO BE A BREAKROOM AND NOT |
| | A KITCHEN. PLEASE LABEL ROOM 113 AS THE |
| | BREAKROOM. |
| | |
| | 8) ON A-103 NOTES 4 AND 5 INCORRECTLY |
| | REFERENCE CODE SECTION 705.1.3.6. PLEASE |
| | CORRECT. SEE FBC 715.4.3. |
| | |
| | 9) THE BREAKROOM SINK IS REQUIRED TO BE |
| | ACCESSIBLE AND COMPLY WITH FBC 11-4.24. |
| | |
| | 10) FIXED OR BUILT-IN SEATING AND TABLES |
| | ARE REQUIRED TO COMPLY WITH FBC 11-4.32. |
| | SEE FIXED SEATING IN BREAKROOM. |
| | |
| | 11) DETAIL MW-14 IS CROSSED OUT ON SHEET |
| | A-104. HOWEVER, IT IS STILL SHOWN ON |
| | A-102. |
| | |
| | 12) THE DOOR TO OFFICE 105 IS REQUIRED |
| | TO HAVE A MINIMUM OF 18" CLEARANCE ON |
| | THE PULL SIDE OF THE DOOR AT THE LATCH |
| | SIDE. SEE FBC 11-4.13.6. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |