2006-10-02 00:00:00SUBMITTED FOR PLAN REVIEW NOT FOR PERMIT
  
  
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE LEVEL OF ALTERATION FOR
 THE PROJECT AS DEFINED IN THE 2004 FBC
 EXISTING BUILDING CODE.
  
 3) SPECIFY THE TYPE OF CONSTRUCTION FOR
 THE BUILDING USING THE 2004 FBC
 DESIGNATION.
  
 4) ON SHEET G-002 BASED ON THE 2004 FBC
 THE BUILDING HEIGHT AND AREA TABLE IS
 503 AND THE TABLE FOR FIRE WALL RATING
 IS 601. PLEASE CORRECT.
  
 5) ON G-002 THE OCCUPANT LOAD FOR 6619
 SQFT IS 67 PERSONS. PLEASE CORRECT.
  
 6) ON G-002 THE EXIT CAPACITY SHOULD BE
 67 X 0.2". PLEASE CORRECT.
  
 7) FBC 1013.2 DOES NOT ALLOW EGRESS TO
 PASS THROUGH A KITCHEN. ROOM 113 ON
 A-102 APPEARS TO BE A BREAKROOM AND NOT
 A KITCHEN. PLEASE LABEL ROOM 113 AS THE
 BREAKROOM.
  
 8) ON A-103 NOTES 4 AND 5 INCORRECTLY
 REFERENCE CODE SECTION 705.1.3.6. PLEASE
 CORRECT. SEE FBC 715.4.3.
  
 9) THE BREAKROOM SINK IS REQUIRED TO BE
 ACCESSIBLE AND COMPLY WITH FBC 11-4.24.
  
 10) FIXED OR BUILT-IN SEATING AND TABLES
 ARE REQUIRED TO COMPLY WITH FBC 11-4.32.
 SEE FIXED SEATING IN BREAKROOM.
  
 11) DETAIL MW-14 IS CROSSED OUT ON SHEET
 A-104. HOWEVER, IT IS STILL SHOWN ON
 A-102.
  
 12) THE DOOR TO OFFICE 105 IS REQUIRED
 TO HAVE A MINIMUM OF 18" CLEARANCE ON
 THE PULL SIDE OF THE DOOR AT THE LATCH
 SIDE. SEE FBC 11-4.13.6.
  