| 2006-12-08 07:53:38 | ****UNSAT 3RD REIVEW ***** |
| | |
| | *** PLEASE KNOW AS SOME ITEMS WERE ADDRESSED FOR THE |
| | MOST PART HOWEVER THERE ARE SOME ITEMS WHICH DO NOT |
| | CORRELATE OR NOT CLEAR FROM PREVIOUS REVIEW. |
| | |
| | |
| | 1) NOTE: PLEASE SHOW THE ATTACHMENT POINT FOR THE |
| | TRANSFORMER. BLDG STEEL, EXISTING GROUNDING ELECTRODE |
| | SYSTEM/RISER IN BLDG ELECTRICAL ROOM? |
| | 250.30, 250.50, 250.58 |
| | BY PLACING THE CONDUCTOR SIZE ON RISER THIS DOES |
| | INDICATE THE ATTACHMENT LOCATION AS PREVIOUSLY |
| | REQUESTED. |
| | |
| | 2) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE FOR |
| | FEEDERS TO THE TRANSFORMER. |
| | PLEASE SEE RISER SHOWS #6'S AND THE PANEL SCHEDULE |
| | SHOWS #8'S. |
| | FBC 106.1.2, |
| | 310.16 |
| | |
| | 3) NOTE: PLEASE SEE LIGHTING POWER DENSITIES ARE NOT |
| | COMPLETED AND SHALL BE INDICATE BY THE DESIGNER. THE |
| | "BLOCK" SHOWING LPD'S PERMITTED IS NOT COMPLETE AT THIS |
| | TIME. |
| | 13-415.2, 13-415.2.ABC.1 |
| | |
| | 4) NOTE: PLEASE SEE THERE IS NO LIGHTING CONTACTOR |
| | DETAIL, SCHEDULE SHOWN AS STATED IN NOTE #3 OF THE KEY |
| | NOTES. |
| | PLEASE SEE NO LCP/LCC IS SHOWN NEXT TO ELECTRICAL PANEL |
| | AS STATED IN NOTE ALSO. |
| | AS STATED IN THE PREVIOUS REVIEW, PLEASE PROVIDE DETAIL |
| | FOR THIS. PLEASE KNOW, ON THIS DETAIL THE EM/EXT LTS |
| | WILL BE SHOWN WIRED AHEAD OF ANY LIGHTING CONTROL PANEL |
| | OR CONTACTOR, AS NOTED IN NOTE #4 OF KEY NOTES PER |
| | 700.12E |
| | |
| | **** ONCE ALL REVIEWS ARE DONE, AND "IF" ALL THE OTHER |
| | REVIEWS HAVE PASSED PLEASE HAVE THE GENERAL CONTRACTOR |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-12-08 06:57:46 | IN PROGRESS |
| 2006-12-07 20:26:11 | REMOVED FROM INCOMING, IN ELECTRIC FOR REVIEW. WILL BE |
| | SENT BACK TO INCOMING ONCE REVIEW IS DONE. |