Plan Review Notes
Plan Review Notes For Permit 06090700
Permit Number 06090700
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-28 11:42:55*** UNSAT 2ND REVIEW***
  
 ** PLEASE SEE SOME NOTE SNOTES FROM PREVIOUS REVIEW AND
 SEE NEW NOTE ADDED TO THE BOTTOM OF NOTES.
 PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW.
 PLEASE SEE NEW NOTE DUE TO CHANGES IN RISER FROM
 PREVIOUS REVIEW.
  
  
 1)A) NOTE: NO, PLEASE SEE NOW SOME SHEETS SHOW #
 1101??
 PLEASE CORRELATE AND BE SURE WORK AND SCOPE OF WORK IS
 LOCATED IN ONE AREA. PLEASE ADJUST PERMIT APPLICATION
 IF NEEDED AND PLEASE BE SURE TO CORRELATE PLANS. PLEASE
 SEE PLANS SHOWS 1203 ON SOME SHEETS AND 1101 ON
 OTHERS???
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SUITE/UNIT # STILL
 NEEDS TO BE VERIFIED. PLEASE KNOW, ONCE
 THE SUITE CORRELATES, THEN PLEASE
 ADJUST. PLEASE SEE PLANS INDICATE 1201,
 THE PERMIT APPLICATION MENTIONS 1203.
 COPY OF PERMIT APPLICATION HAS BEEN SENT
 TO ADDRESSING.
  
 1) NOTE: OK.
  
 2) NOTE:NO, QUOTING THE SAME CODE GIVEN IN NOTES IN
 LIEU OF TECHNICAL DETAIL OR INFORMATION IS NOT
 PERMITTED.
 PLEASE SEE RISER IS STILL SHOWING A NEUTRAL FROM THE
 PANEL "HP" TO TRANSFORMER.
 SEE NEW NOTES FOR CONDUCTORS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE GROUNDING
 ELECTRODE CONDUCTOR AND ATTACHMENT FOR
 THE NEW TRANSFORMER. PER 250.66,250.24,
 250.30, 250.20 ETC.
  
 3) NOTE: OK SEEMS DOORS ARE REMOVED HOWEVER SEE THE
 NEXT COMMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE TRANSFORMER LOCATION
 MAY NOT BE LOCATED IN A STORAGE CLOSET.
 PLEASE SEE MIN CLEARANCES PER
 450.9,450.13, 110.26 ETC.
  
 4) NOTE: NO, THIS IS THE SAME NOTE. PLEASE SEE THE
 LENGTH OF TAPPED CONDUCTORS FROM TRANSFORMER DOES NOT
 MEET PREVIOUS NOTE .
 PLEASE SEE 240.21, THE MCB WAS ADDED TO "LP1" HOWEVER
 THE LENGHT OF CONDUCTORS WOULD FARTHER THAN 10FT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE ALSO SEE 240.21 AS THE
 DISTANCE OF THE TAPPED CONDUCTORS FROM
 THE SECONDARY SIDE OF THE TRANSFORMER
 DOES NOT SEEM TO MEET CODE. PLEASE SEE
 10FT OF CONDUCTOR TAP RULE.
 PLEASE SEE IT IS UNCLEAR OF THE PANEL
 LP1 CONTAINS A MCB WITH OCP??
 408.16, 240.21
  
 5) NOTE: OK.
  
 6) NOTE:NO, NO INFORMATION SHOWN FOR NOTE #3 OF KEY
 NOTES ON LIGHTING PLAN.??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE MINIMUM LIGHTING
 CONTROL SYSTEM AS PROPOSED IN NOTE #3 OF
 KEY NOTES, NEEDS TO BE SHOWN. PLEASE
 ALSO SEE SOME AREAS OF INGRESS AND
 EGRESS SPACE REQUIRES THE OVER-RIDE
 DEVICES SO THAT THE OCCUPANT CAN SEE THE
 LIGHTING WHICH IS BEING OVER-RIDDEN.
 PLEASE PROVIDE THESE DEVICES AT THE
 LOCATION(S) AS MENTIONED.
 PLEASE VERIFY THE RECEPT/WORK OFFICE
 STATION AREA, AS THIS AREA SEEM TO HAVE
 ONE OCCUPANT SENSOR TYPE DEVICE WHICH
 OPERATES LT'S IN ANOTHER ARE. THIS WAS
 RED-LINED ON PLANS.
 PLEASE PROVIDE MIN LIGHTING DENSITIES
 BEING AS SHOWN .
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
 PLEASE SEE 13-415.2.ABC.1, AND TABLES.
  
 7) NOTE:NO, AND PLEASE SEE NEW NOTES AS MAIN HAS
 CHANGED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE STATE THE AIC RATING TO
 NEW MAIN DISCONNECT. 110.9., 240.12
  
 *** NEW NOTE ***
  
 8) NOTE: PLEASE SEE NOTE BELOW WHICH WAS AS***
 IMPORTANT*** HOWEVER THIS WAS NOT DONE. PLEASE KNOW IF
 PLANS COME BACK WITH THE OLD/VOIDED SHEETS IN SETS,
 PLANS WILL BE PLACED OUT FRONT FOR PICK UP UNTIL THIS
 IS DONE.
 PLEASE KNOW AS PREVIOUSLY MENTIONED, THIS ONLY DELAYS
 THE REVIEW PROCESS AND ISSUANCE OF PERMIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 9) NOTE: PLEASE SEE RISER HAS NOW CHANGED TO 150A'S,
 YET PANEL "H" REMAINS 100A'S??
 PLEASE SEE PREVIOUS PLANS SHOWED 100A MAIN.
 PLEASE CORRELATE, RISER PANEL SCHEDULE CONDUCTORS ETC
 ETC.
  
 10) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-10-27 21:16:04*** IN ELECTRICAL FOR REVIEW***
  
  
 ALL OLD/VOIDED SHEETS WHICH WERE REQUESTED TO BE
 REMOVED ON PREVIOUS REVIEW WERE NOT.
 PLEASE KNOW, THIS ONLY CAUSES DELAYS IN REVIEWING AND
 STAMPING OF PLANS AS PREVIOUSLY NOTED.
 THIS WAS NOTED AS** IMPORTANT**.