| 2006-10-28 11:42:55 | *** UNSAT 2ND REVIEW*** |
| | |
| | ** PLEASE SEE SOME NOTE SNOTES FROM PREVIOUS REVIEW AND |
| | SEE NEW NOTE ADDED TO THE BOTTOM OF NOTES. |
| | PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW. |
| | PLEASE SEE NEW NOTE DUE TO CHANGES IN RISER FROM |
| | PREVIOUS REVIEW. |
| | |
| | |
| | 1)A) NOTE: NO, PLEASE SEE NOW SOME SHEETS SHOW # |
| | 1101?? |
| | PLEASE CORRELATE AND BE SURE WORK AND SCOPE OF WORK IS |
| | LOCATED IN ONE AREA. PLEASE ADJUST PERMIT APPLICATION |
| | IF NEEDED AND PLEASE BE SURE TO CORRELATE PLANS. PLEASE |
| | SEE PLANS SHOWS 1203 ON SOME SHEETS AND 1101 ON |
| | OTHERS??? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE SUITE/UNIT # STILL |
| | NEEDS TO BE VERIFIED. PLEASE KNOW, ONCE |
| | THE SUITE CORRELATES, THEN PLEASE |
| | ADJUST. PLEASE SEE PLANS INDICATE 1201, |
| | THE PERMIT APPLICATION MENTIONS 1203. |
| | COPY OF PERMIT APPLICATION HAS BEEN SENT |
| | TO ADDRESSING. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE:NO, QUOTING THE SAME CODE GIVEN IN NOTES IN |
| | LIEU OF TECHNICAL DETAIL OR INFORMATION IS NOT |
| | PERMITTED. |
| | PLEASE SEE RISER IS STILL SHOWING A NEUTRAL FROM THE |
| | PANEL "HP" TO TRANSFORMER. |
| | SEE NEW NOTES FOR CONDUCTORS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE GROUNDING |
| | ELECTRODE CONDUCTOR AND ATTACHMENT FOR |
| | THE NEW TRANSFORMER. PER 250.66,250.24, |
| | 250.30, 250.20 ETC. |
| | |
| | 3) NOTE: OK SEEMS DOORS ARE REMOVED HOWEVER SEE THE |
| | NEXT COMMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE TRANSFORMER LOCATION |
| | MAY NOT BE LOCATED IN A STORAGE CLOSET. |
| | PLEASE SEE MIN CLEARANCES PER |
| | 450.9,450.13, 110.26 ETC. |
| | |
| | 4) NOTE: NO, THIS IS THE SAME NOTE. PLEASE SEE THE |
| | LENGTH OF TAPPED CONDUCTORS FROM TRANSFORMER DOES NOT |
| | MEET PREVIOUS NOTE . |
| | PLEASE SEE 240.21, THE MCB WAS ADDED TO "LP1" HOWEVER |
| | THE LENGHT OF CONDUCTORS WOULD FARTHER THAN 10FT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE ALSO SEE 240.21 AS THE |
| | DISTANCE OF THE TAPPED CONDUCTORS FROM |
| | THE SECONDARY SIDE OF THE TRANSFORMER |
| | DOES NOT SEEM TO MEET CODE. PLEASE SEE |
| | 10FT OF CONDUCTOR TAP RULE. |
| | PLEASE SEE IT IS UNCLEAR OF THE PANEL |
| | LP1 CONTAINS A MCB WITH OCP?? |
| | 408.16, 240.21 |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE:NO, NO INFORMATION SHOWN FOR NOTE #3 OF KEY |
| | NOTES ON LIGHTING PLAN.?? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE MINIMUM LIGHTING |
| | CONTROL SYSTEM AS PROPOSED IN NOTE #3 OF |
| | KEY NOTES, NEEDS TO BE SHOWN. PLEASE |
| | ALSO SEE SOME AREAS OF INGRESS AND |
| | EGRESS SPACE REQUIRES THE OVER-RIDE |
| | DEVICES SO THAT THE OCCUPANT CAN SEE THE |
| | LIGHTING WHICH IS BEING OVER-RIDDEN. |
| | PLEASE PROVIDE THESE DEVICES AT THE |
| | LOCATION(S) AS MENTIONED. |
| | PLEASE VERIFY THE RECEPT/WORK OFFICE |
| | STATION AREA, AS THIS AREA SEEM TO HAVE |
| | ONE OCCUPANT SENSOR TYPE DEVICE WHICH |
| | OPERATES LT'S IN ANOTHER ARE. THIS WAS |
| | RED-LINED ON PLANS. |
| | PLEASE PROVIDE MIN LIGHTING DENSITIES |
| | BEING AS SHOWN . |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND |
| | .1.3. |
| | PLEASE SEE 13-415.2.ABC.1, AND TABLES. |
| | |
| | 7) NOTE:NO, AND PLEASE SEE NEW NOTES AS MAIN HAS |
| | CHANGED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE STATE THE AIC RATING TO |
| | NEW MAIN DISCONNECT. 110.9., 240.12 |
| | |
| | *** NEW NOTE *** |
| | |
| | 8) NOTE: PLEASE SEE NOTE BELOW WHICH WAS AS*** |
| | IMPORTANT*** HOWEVER THIS WAS NOT DONE. PLEASE KNOW IF |
| | PLANS COME BACK WITH THE OLD/VOIDED SHEETS IN SETS, |
| | PLANS WILL BE PLACED OUT FRONT FOR PICK UP UNTIL THIS |
| | IS DONE. |
| | PLEASE KNOW AS PREVIOUSLY MENTIONED, THIS ONLY DELAYS |
| | THE REVIEW PROCESS AND ISSUANCE OF PERMIT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | 9) NOTE: PLEASE SEE RISER HAS NOW CHANGED TO 150A'S, |
| | YET PANEL "H" REMAINS 100A'S?? |
| | PLEASE SEE PREVIOUS PLANS SHOWED 100A MAIN. |
| | PLEASE CORRELATE, RISER PANEL SCHEDULE CONDUCTORS ETC |
| | ETC. |
| | |
| | 10) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-10-27 21:16:04 | *** IN ELECTRICAL FOR REVIEW*** |
| | |
| | |
| | ALL OLD/VOIDED SHEETS WHICH WERE REQUESTED TO BE |
| | REMOVED ON PREVIOUS REVIEW WERE NOT. |
| | PLEASE KNOW, THIS ONLY CAUSES DELAYS IN REVIEWING AND |
| | STAMPING OF PLANS AS PREVIOUSLY NOTED. |
| | THIS WAS NOTED AS** IMPORTANT**. |