| Plan Review Notes For Permit 06090700 |
| Permit Number |
06090700 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-03 15:11:39 | | | | DENIED BY BUILDING | | | | | | 1) THE LEVEL OF ALTERATION FOR THIS PROJECT IS LEVEL 2, | | | NOT LEVEL 1. PLEASE CORRECT ON SHEET A.0. SEE 2004 FBC | | | EXISTING BUILDING CODE SECTION 304. | | | | | | 2) ON SHEET LS.1, THE CONSTRUCTION TYPE IS INCORRECTLY | | | SPECIFIED AS TYPE V-B. THE CONSTRUCTION TYPE LISTED ON | | | SHEET A.0 IS TYPE I-A. PLEASE CORRECT. | | | | | | 3) ON LS.1, THE OCCUPANT LOAD CALCULATIONS ARE | | | INCORRECT. THE OCCUPANCY IS BUSINESS NOT MERCANTILE. | | | THE FLOOR AREA FOR OCCUPANT IS 100 GROSS. SEE FBC TABLE | | | 1004.1.2. PLEASE CORRECT. | | | AREA IS 3000 SQFT DIVIDED BY 100 WHICH EQUALS 30 | | | PERSONS. | | | | | | 4) THE REQUIRED EGRESS WIDTH IS 30 TIMES 0.2EQUALS 6 | | | INCHES. HOWEVER, FBC 1008.1.1 REQUIRES EGRESS DOORS TO | | | HAVE A MINIMUM CLEAR WIDTH OF 32 INCHES. SEE NOTATIONS | | | ON SHEET LS.1 OF ONE OF THE PLAN SETS. | | | | | | 5)ON SHEETS ET.1 AND D.1 PORTIONS OF THE EXISTING | | | WALLS APPEAR TO BE MISSING. PLEASE CORRECT. | | | | | | 6)SPECIFY THE FIRE RATING OF THE NEW WALLS THAT ARE | | | PART OF THE EXISTING FIRE RATED CORRIDOR. INDICATE | | | THESE WALLS ON THE PLANS. PROVIDE WALL SECTIONS AND | | | ASSEMBLY NUMBERS. | | | | | | 7) SPECIFY THE REQUIRED FIRE RATING OF THE TWO NEW | | | EGRESS DOORS IN THE FIRE RATED CORRIDOR. PROVIDE ID | | | TAGS FOR THE DOORS THAT WILL TIE THEM TO THE DOOR | | | SCHEDULE ON SHEET A.4. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|