Notes
Date Text
2006-10-03 00:00:00DENIED;
 1.DOOR SWING IN BREAK ROOM AND SHOWER
 ROOM SWINGS INTO THE CLEAR FLOOR SPACE
 OF THE HANDICAP FIXTURES.
 2.SANITARY RISER DIAGRAM; SHOWER IS NOT
 VENTED.
 3.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 REQUIRED TO BE 3". SEE SECTION406.3.
 4.BREAK SINK NOT IN SAME LOCATION AS
 FLOOR PLAN (DETAIL ON PAGE LS.1 #3)
 5.WATER HEATER DETAIL PAGE P.1 THERMAL
 EXPANTION CONTROL REQUIRED. SECTION
 607.3 SHOW TYPE AND LOCATION.
 6.SHOW TERMINATION POINT OF PAN DRAIN
 AND RELIEF LINE, ALSO SIZE OF PIPE USED.
 7.AIR ADMITTANCE VALVES CAN ONLY BE USED
 ON THE TOP 4 BRANCH INTERVALS. SECTION
 917.3.1 IS THERE 3 FLOORS OR LESS ABOVE
 THE 12 TH FLOOR?
 8.WATER RISER DIAGRAM; SHOW WATER HANNER
 ARRESTORS WHERE REQUIRED ON PLANS AND
 SPEC OUT SIZE AND MANUFACTURE.
 PLUMBING PLAN REVIEW BY;