| Plan Review Notes For Permit 06090700 |
| Permit Number |
06090700 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-03 00:00:00 | DENIED; | | | 1.DOOR SWING IN BREAK ROOM AND SHOWER | | | ROOM SWINGS INTO THE CLEAR FLOOR SPACE | | | OF THE HANDICAP FIXTURES. | | | 2.SANITARY RISER DIAGRAM; SHOWER IS NOT | | | VENTED. | | | 3.AUTOMATIC CLOTHES WASHER BRANCH DRAIN | | | REQUIRED TO BE 3". SEE SECTION406.3. | | | 4.BREAK SINK NOT IN SAME LOCATION AS | | | FLOOR PLAN (DETAIL ON PAGE LS.1 #3) | | | 5.WATER HEATER DETAIL PAGE P.1 THERMAL | | | EXPANTION CONTROL REQUIRED. SECTION | | | 607.3 SHOW TYPE AND LOCATION. | | | 6.SHOW TERMINATION POINT OF PAN DRAIN | | | AND RELIEF LINE, ALSO SIZE OF PIPE USED. | | | 7.AIR ADMITTANCE VALVES CAN ONLY BE USED | | | ON THE TOP 4 BRANCH INTERVALS. SECTION | | | 917.3.1 IS THERE 3 FLOORS OR LESS ABOVE | | | THE 12 TH FLOOR? | | | 8.WATER RISER DIAGRAM; SHOW WATER HANNER | | | ARRESTORS WHERE REQUIRED ON PLANS AND | | | SPEC OUT SIZE AND MANUFACTURE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|