Plan Review Notes
Plan Review Notes For Permit 06090700
Permit Number 06090700
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-03 00:00:00*****DENIED*****
  
  
  
 1.) VERIFY/RECTIFY THE SUITE NUMBER OF
 WHERE THE SCOPE OF THE WORK IS GOING TO
 BE DONE. THE APPLICATION HAS SUITE 1203,
 WHEREAS THE PLANS HAVE SUITE 1201.
  
 2.) STRUCTURES UNDERGOING CONSTUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF THE
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 4.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES DURING ALTERATION.
  
 5.) WHEN IT IS NECESSARY TO SHUT DOWN A
 FIRE PROTECTION SYSTEM, THE FIRE
 DEPARTMENT WILL BE NOTIFIED WHEN THE
 SYSTEM IS SHUT DOWN AND WHEN IT IS
 RETURNED TO SERVICE.
  
 6.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE
 FIRE SPRINKLER OR FIRE ALARM SYSTEM,
 SEPARATE PERMIT AND SHOP DRAWINGS/PLANS
 ARE REQUIRED.
  
 7.) INTERIOR FINISH FOR WALLS AND
 CEILINGS IN EXITS AND EGRESS CORRIDORS
 SHALL BE CLASS "A" OR CLASS "B".
  
 8.) INDICATE ON THE PLANS THE LOCATION
 OF FIRE PROTECTION SYSTEMS(I.E.
 SPRINKLER HEADS, SMOKE ALARMS, PULL
 STATIONS, FIRE EXTINGUISHER(S), AUDIO
 AND/OR VISUAL DEVICES, DUCT DETECTORS,
 ETC.) FOR THE EXISTING AS WELL AS THE
 PROPOSED LAYOUT OF THE TENANT SPACE.
  
  
 **PLEASE SUBMIT OR ADDRESS THE ABOVE
 INFORMATION FOR REVIEW.**
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW