Plan Review Notes
Plan Review Notes For Permit 06090700
Permit Number 06090700
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-30 00:00:00*** UNSAT ***
  
  
 1)A) NOTE: PLEASE SEE SUITE/UNIT # STILL
 NEEDS TO BE VERIFIED. PLEASE KNOW, ONCE
 THE SUITE CORRELATES, THEN PLEASE
 ADJUST. PLEASE SEE PLANS INDICATE 1201,
 THE PERMIT APPLICATION MENTIONS 1203.
 COPYOF PERMIT APPLICATION HAS BEEN SENT
 TO ADDRESSING.
  
 1) NOTE: PLEASE VERFIFY MISSING
 EQUIPMENT GROUNDING CONUDCTOR FROM
 BUS-TAP DISC TO THE METER. PLEASE ALSO
 INDICATE "FLOATING NEUTRAL" AT THE METER
 AT THIS IS AFTER THE FIRST MEANS OF
 DISCONNECT FOR TRHE BUILDING.
 250.6,250.24., 250.110, 250.122
  
 2) NOTE: PLEASE INDICATE THE GROUNDING
 ELECTRODE CONDUCTOR AND ATTACHMENT FOR
 THE NEW TRANSFORMER. PER 250.66,250.24,
 250.30, 250.20 ETC.
  
 3) NOTE: PLEASE SEE TRANSFORMER LOCATION
 MAY NOT BE LOCATED IN A STROAGE CLOSET.
 PLEASE SEE MIN CLEARENCES PER
 450.9,450.13, 110.26 ETC.
  
 4) NOTE: PLEASE ALSO SEE 240.21 AS THE
 DISTANCE OF THE TAPPED CONDUCTORS FROM
 THE SECONDARY SIDE OF THE TRANSFORMER
 DOES NOT SEEM TO MEET CODE. PLEASE SEE
 10FT OF CONDUCTOR TAP RULE.
 PLEASE SEE IT IS UNCLEAR OF THE PANEL
 LP1 CONTAINS A MCB WITH OCP??
 408.16, 240.21
  
 5) NOTE: PLEASE SEE PLANS FROM A- SHEETS
 TO MEP, SEEM TO INDICATE A "STACKABLE
 WASHER/DRYER UNTI , HOWEVER THE LOAD
 CALCULATIONS AND ELECTRICAL PLANS DO NOT
 SEEM TO CORRELATE WITH THIS. PLEASE
 VERIFY AND ADJUST.
 ** PLEASE KNOW, UNDER THE NEW 2005 CODE
 WHICH IS NOT YERT IN EFFECT, THIS WOULD
 REQUIRE BOTH OF THESE CIRCUITS OR EVEN
 ONE TO BE GFI PROTECTED. THIS IS ONLY
 FOR INFORMATIONAL PURPOSE AS THIS
 PROJECT IS UNDER THE 2002 NEC.
  
 6) NOTE: PLEASE SEE THE MINIMUM LIGHTING
 CONTROL SYSTEM AS PROPOSED IN NOTE #3 OF
 KEY NOTES, NEEDS TO BE SHOWN. PLEASE
 ALSO SEE SOME AREAS OF INGRESS AND
 EGRESSINTO SPACE REQUIRES THE OVER-RIDE
 DEVICES SO THAT THE OCCUPANT CAN SEE THE
 LIGHTING WHICH IS BEING OVER-RIDEN.
 PLEASE PROVIDE THESE DEVICES AT THE
 LOCATION(S) AS MENTIONED.
 PLEASE VERIFY THE RECEPT/WORK OFFICE
 STATION AREA, AS THIS AREA SEEM TO HAVE
 ONE OCCUPANT SENSOR TYOE DEVICE WHICH
 OPERATES LTS IN ANOTHER ARE. THIS WAS
 REDLINED ON PLANS.
 PLEASE PROVIDE MIN LIGHTING DENSITIES
 BEING AS SHOWN .
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
 PLEASE SEE 13-415.2.ABC.1, AND TABLES.
  
 7) NOTE: PLEASE STATE THE AIC RATING TO
 NEW MAIN DISCONNECT. 110.9.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-09-29 00:00:00IN ELEC FOR REVIEW