| Date |
Text |
| 2006-09-30 00:00:00 | *** UNSAT *** |
| | |
| | |
| | 1)A) NOTE: PLEASE SEE SUITE/UNIT # STILL |
| | NEEDS TO BE VERIFIED. PLEASE KNOW, ONCE |
| | THE SUITE CORRELATES, THEN PLEASE |
| | ADJUST. PLEASE SEE PLANS INDICATE 1201, |
| | THE PERMIT APPLICATION MENTIONS 1203. |
| | COPYOF PERMIT APPLICATION HAS BEEN SENT |
| | TO ADDRESSING. |
| | |
| | 1) NOTE: PLEASE VERFIFY MISSING |
| | EQUIPMENT GROUNDING CONUDCTOR FROM |
| | BUS-TAP DISC TO THE METER. PLEASE ALSO |
| | INDICATE "FLOATING NEUTRAL" AT THE METER |
| | AT THIS IS AFTER THE FIRST MEANS OF |
| | DISCONNECT FOR TRHE BUILDING. |
| | 250.6,250.24., 250.110, 250.122 |
| | |
| | 2) NOTE: PLEASE INDICATE THE GROUNDING |
| | ELECTRODE CONDUCTOR AND ATTACHMENT FOR |
| | THE NEW TRANSFORMER. PER 250.66,250.24, |
| | 250.30, 250.20 ETC. |
| | |
| | 3) NOTE: PLEASE SEE TRANSFORMER LOCATION |
| | MAY NOT BE LOCATED IN A STROAGE CLOSET. |
| | PLEASE SEE MIN CLEARENCES PER |
| | 450.9,450.13, 110.26 ETC. |
| | |
| | 4) NOTE: PLEASE ALSO SEE 240.21 AS THE |
| | DISTANCE OF THE TAPPED CONDUCTORS FROM |
| | THE SECONDARY SIDE OF THE TRANSFORMER |
| | DOES NOT SEEM TO MEET CODE. PLEASE SEE |
| | 10FT OF CONDUCTOR TAP RULE. |
| | PLEASE SEE IT IS UNCLEAR OF THE PANEL |
| | LP1 CONTAINS A MCB WITH OCP?? |
| | 408.16, 240.21 |
| | |
| | 5) NOTE: PLEASE SEE PLANS FROM A- SHEETS |
| | TO MEP, SEEM TO INDICATE A "STACKABLE |
| | WASHER/DRYER UNTI , HOWEVER THE LOAD |
| | CALCULATIONS AND ELECTRICAL PLANS DO NOT |
| | SEEM TO CORRELATE WITH THIS. PLEASE |
| | VERIFY AND ADJUST. |
| | ** PLEASE KNOW, UNDER THE NEW 2005 CODE |
| | WHICH IS NOT YERT IN EFFECT, THIS WOULD |
| | REQUIRE BOTH OF THESE CIRCUITS OR EVEN |
| | ONE TO BE GFI PROTECTED. THIS IS ONLY |
| | FOR INFORMATIONAL PURPOSE AS THIS |
| | PROJECT IS UNDER THE 2002 NEC. |
| | |
| | 6) NOTE: PLEASE SEE THE MINIMUM LIGHTING |
| | CONTROL SYSTEM AS PROPOSED IN NOTE #3 OF |
| | KEY NOTES, NEEDS TO BE SHOWN. PLEASE |
| | ALSO SEE SOME AREAS OF INGRESS AND |
| | EGRESSINTO SPACE REQUIRES THE OVER-RIDE |
| | DEVICES SO THAT THE OCCUPANT CAN SEE THE |
| | LIGHTING WHICH IS BEING OVER-RIDEN. |
| | PLEASE PROVIDE THESE DEVICES AT THE |
| | LOCATION(S) AS MENTIONED. |
| | PLEASE VERIFY THE RECEPT/WORK OFFICE |
| | STATION AREA, AS THIS AREA SEEM TO HAVE |
| | ONE OCCUPANT SENSOR TYOE DEVICE WHICH |
| | OPERATES LTS IN ANOTHER ARE. THIS WAS |
| | REDLINED ON PLANS. |
| | PLEASE PROVIDE MIN LIGHTING DENSITIES |
| | BEING AS SHOWN . |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND |
| | .1.3. |
| | PLEASE SEE 13-415.2.ABC.1, AND TABLES. |
| | |
| | 7) NOTE: PLEASE STATE THE AIC RATING TO |
| | NEW MAIN DISCONNECT. 110.9. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2006-09-29 00:00:00 | IN ELEC FOR REVIEW |