Plan Review Notes
Plan Review Notes For Permit 06090700
Permit Number 06090700
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-28 00:00:00DENIED BY BUILDING
  
 1) SPECIFY THE LEVEL OF ALTERATION FOR
 THE WORK AS SPECIFIED IN THE 2004 FBC
 EXISTING BUILDING CODE.
  
 2) SPECIFY THE BUILDING HEIGHT AND
 NUMBER OF STORIES.
  
 3) THE CONSTRUCTION TYPE SPECIFIED FOR
 THIS BUILDING IS INCORRECT. SEE 2004 FBC
 TABLE 503 FOR ALLOWABLE HEIGHTS AND
 AREAS.
  
 4) ON SHEET LS.1, THE OCCUPANCY TYPE AND
 OCCUPANT LOAD ARE INCORRECT. SEE FBC 302
 AND TABLE 1004.1.2.
  
 5) SUBMIT A DEMOLITION PLAN OR FLOOR
 PLAN SHOWING THE EXISTING CONDITION OF
 THE SPACE PRIOR TO THE PROPOSED
 CONSTRUCTION.
  
 6) ON SHEET LS.1 THE MAXIMUM DEAD END
 CORRIDOR IS INCORRECTLY SPECIFIED AS 5'.
 SEE FBC 1016.3 EXCEPTION (2) WHICH
 ALLOWS 50' MAX DEAD END CORRIDOR LENGTH
 IN FULLY SPRINKLERED BUSINESS
 OCCUPANCIES.
  
 7) FBC TABLE 803.5 REQUIRES INTERIOR
 WALL AND CEILING FINISHES TO BE CLASS B
 IN VERTICAL EXITS AND EXIT PASSAGEWAYS.
 PLEASE REVISE ON SHEET A.1.
  
 8) THE DOOR AT THE SHOWER ROOM CAN NOT
 SWING INTO THE REQUIRED FLOOR SPACE FOR
 THE LAVATORY. SEE FBC 11-4.23.2.
  
 9) THE BREAKROOM CABINET ELEVATION ON
 LS.1 SPECIFIES THE 2001 FBC. PLEASE
 UPDATE TO 2004 FBC.
  
 10) ON LS.1 THE BREAKROOM CABINET
 ELEVATION DOES NOT CORRESPOND TO THE
 FLOOR PLANS. PLEASE CORRECT. THE DOOR
 ALSO SWINGS INTO THE CLEAR FLOOR SPACE
 AT THE SINK.
  
 11) FBC 11-4.24.4 LIMITS SINKS TO A
 MAXIMUM DEPTH OF 6-1/2 INCHES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  