| 2007-09-13 13:41:09 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE THE NEW SEPARATE ELECTRICAL SERVICE |
| | AND METER LOCATION WOULD BE UNDER A SEPARATE PERMIT FOR |
| | THE SERVICE. THIS IS NOT ACTUALLY COMING FROM THE |
| | BUILDING ELECTRICAL SERVICE OR ANY PART OF THE |
| | BUILDING. |
| | PLEASE SEE THIS LOCATION WILL ALSO REQUIRE AN ADDRESS |
| | EXTENSION TO PCN FOR NEW METER/SERVICE LOCATION. PLEASE |
| | BE SURE TO GET WITH THE FPL REPRESENTATIVE AND THE CITY |
| | ADDRESSING REVIEWER LILI LACRAMIOARA @ 561-822-1239. |
| | |
| | 2) NOTE: PLEASE CLARIFY RISER AS THIS SHOWS A *GROUND* |
| | ON THE LINE SIDE OF THE FIRST MEANS OF DISCONNECT. IS |
| | THIS THE NEUTRAL/GROUNDED CONDUCTOR? |
| | NO *EQUIPMENT GROUNDING CONDUCTORS* ARE ALLOWED ON THE |
| | LINE SIDE OF SERVICE MAINS. |
| | 250.6, 250.24 |
| | |
| | 3) NOTE: TWO GROUND RODS MINIMUM WILL BE REQUIRED PER |
| | 250.50 AND 250.56 |
| | |
| | 4) NOTE: PLEASE PROVIDE INFORMATION FOR PUMP SIZE AND |
| | OVER CURRENT PROTECTION INFORMATION. |
| | REVIEW OF SOME ITEMS FOR CONDUCTOR SIZES, SERVICE ETC |
| | CAN NOT BE REVIEWED AT THIS TIME. |
| | |
| | ** PLEASE KNOW THE ABOVE ELECTRICAL WILL NEED TO BE |
| | SUBMITTED UNDER AN ELECTRICAL PERMIT FOR THE NEW |
| | SEPARATE SERVICE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |